8 Operating
8.4.1 Menu 1: "Test & Status Menu"
Overview:
Start functiontest
Start durationtest
Main menu
Cancel durationtest
Test & status menu
Sum failure info
Block & reset alarms
etc.
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Start functiontest
Menu 1
Start durationtest
Start functiontest
Cancel durationtest
Start durationtest
Sum failure info
Cancel durationtest
etc.
Sum failure info
Circuit state
Luminaire state
DLS/TLS/3PhW state
Charging/Bat. state
Relay state
Substation state
Start functiontest
Start durationtest
 Selection of
Cancel durationtest
Sum failure info
menu options
etc.
with the keys
 <ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes
entered are
Start functiontest
saved)
Start durationtest
Cancel durationtest
 <ESC>: cancel
Sum failure info
and return to
etc.
the previous
menu (any
changes en-
tered are not
saved)
 flashing input
prompt
Start functiontest
Start durationtest
Cancel durationtest
Sum failure info
Circuit state
etc.
78
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
 <ok>
Menu 1.1: Request in view of the of station
to be tested (M3-Mode, compare note M3)
 <ok> initiates a function test for the
connected final circuits:
The LC display shows the main screen
with the message "Function test" .
 <ok>
Menu 1.2: Request in view of the station
(M3-Mode/compare note M3)
 <ok> initiates an battery duration test:
The LC display shows the main screen with
the message "Operating duration test" and
the length of the test (up to the preset rated
operation time). (see menu 3.20 "Serial
number and type")
 <ok>
Menu 1.3: Request in view of the station
(M3-Mode/compare note M3)
 <ok> iniciates the abort of the running
duration testcancels an operating duration
test which is in progress.
The main screen reappears showing mes-
sages about the current operation of the
system.
 <ok>
Menu 1.4: Displays the list of fault mes-
sages.
 <ok>
SKU 2/1  circuit:1 
Menu
Status display
1.5:
Add. information
Circuit name
Line 2: Possible status displays:
Circuit blocked
Battery operation
Normal operation
Function test pre-run
Function test
Mains emergency operation
A battery test run (5 min.) is performed after
a short mains operation (5 min.).
The main screen displays a fault message
if a fault is detected.
Further information can be polled in the
following submenus of the Test & Status
Menu (e.g. "1.4 Group fault info" etc.).
Cancel: <Menu> key and then select "B-
Test cancel" ,
If the preset limit operating duration is not
achieved (see menu 3.20 "Serial number
and type"), the main screen displays the
message "Charge/battery failure" .
If this happens the battery set must be
tested and replaced if necessary!
Note M3
In the Multi-Master-Mode this
operation can be effected at any
station of the system:
this device
all devices
Device address 01
Device name
Device address referes to search
results in the substation setup
menu 3 «Basic settings»
 Successive polling with 
If a number of fault messages have ac-
cumulated, they can be viewed in succes-
sion on the LC display.
Sum failure
List:
Failure 1
Failure 2
Failure 3
etc.
 Select input field with 
 Select installed SKUs or the circuits set
up under circuit setup with 
 Finish and return to Menu 3 with
<Menu> or <ESC>
Line 3: Displays the additional infor-
mation, e.g. «Waiting for SKU data» or
«FT-Current value 1,2A»