Service Manual 5. Electrical Part 5.1 Wiring Diagram ●Instruction Symbol Symbol Color Symbol Symbol Color Symbol Name White GREEN COMP Compressor Yellow Brown Grouding wire Blue YEGN Yellow/Green Black Violet Orange ● Outdoor Unit MULTIU18HP230V1DO 60000706049101 Technical Information...
Page 16
Service Manual MULTIU42HP230V1DO θ θ θ θ θ θ θ θ θ θ θ θ θ θ 600007060630 These circuit diagrams are subject to change without notice, please refer to the one supplied with the unit. Technical Information...
Service Manual 5.2 PCB Printed Diagram MULTIU18HP230V1DO MULTIU24HP230V1DO ● TOP VIEW 2 3 4 5 6 10 11 12 13 Compressor three phase input interface Terminal of system low pressure protection Terminal of system high pressure protection Overload interface of compressor Interface of Inhalation temperature package...
Page 18
Service Manual MULTIU36HP230V1DO MULTIU42HP230V1DO ● TOP VIEW 2 3 4 Compressor three phase input interface Terminal of system low pressure protection Terminal of system high pressure protection Overload interface of compressor Interface of temperature sensor 6 Air valve temperature package Liquid valve temperature package Terminal of electronic...
Service Manual 6. Function and Control 1.Function Control 1) Cooling mode a. Turning on the unit for cooling operation, and if any one of the indoor units satisfy the cooling operation condition, the system will start for cooling operation; and the electronic expansion valve, the outdoor fan and the compressor start operation. b.
Page 20
Service Manual 3) High exhaust temperature protection If the exhaust temperature is higher than protection value, the compressor stops running. If the exhaust temperature protection continuously appears for 6 times, the compressor can’t resume running. In this case, only by cutting off the power and then reenergize that the compressor can restart.
Service Manual Part Ⅱ : Installation and Maintenance 7. Safety Precautions Forbidden Items! It indicates that improper operation might lead to human casualty or sever injury. Items need to be followed. It indicates that improper operation might lead to personal injury or property damage. Installation should be conducted by Follow this instruction to complete the dealer or qualified personnel.
Page 22
Service Manual Main Tools for Installation and Maintenance 1. Level meter, measuring tape 2. Screw driver 3. Impact drill, drill head, electric drill 4. Electroprobe 5. Universal meter 6. Torque wrench, open-end wrench, inner hexagon spanner 7. Electronic leakage detector 8.
Service Manual 8. Installation Manual Installation procedures Start installation Preparation before installation Read the requirements select installation Prepare tools for electric connection location Select indoor unit Select outdoor unit installation location installation location Install wall-mounting Install the support of outdoor unit (select it according to the actual situation) frame, drill wall holes Connect pipes of indoor...
Service Manual 8.1 Preparation before Installation 8.1.1 Standard parts Please use the following standard parts supplied by GREE. Pars of Outdoor Unit Remark Namber name Quantity picture Owner’s manual Tube connector 18/24/36K:8; 42K:9 subassy 8.1.2 Selecting installation site Forbidden Items! It indicates that improper operation might lead to human casualty or sever injury.
Page 25
Service Manual When the outdoor unit is totally surrounded by walls, the installation space of the unit should be as required in Fig.1. >39 3/8 > 19 2/3 >78 3/4 > 19 2/3 >78 3/4 unit:inch Fig.1 8.1.3 Piping Connection The maximum pipe length is shown in the following table.
Service Manual 8.2 Installation Instruction 8.2.1 Outline and dimension of the outdoor unit NAME OF PARTS WARNING ● If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard. ●...
Page 27
Service Manual ELECTRICAL CONNECTIONS MULTIU18HP230V1DO 1. Remove the handle at the right side plate of the outdoor unit (one screw). 2. Remove the cable clamp, connect the power connection cable with the terminal at the row of connection and fix the connection. The fitting line distributing must be consistent with the indoor unit.
Page 28
Service Manual Safety Precautions INSTALLING THE OUTDOOR UNIT Please read this manual carefully before using and operating MULTIU36HP230V1DO Please especially take notice of the following two symbols: Location Use bolts to secure the unit to a flat, solid floor.When Warning! It indicates improper operation which will le mounting the unit on a wall or the roof, make sure the support Caution! It indicates improper operation which will lea is firmly secured so that it cannot move in the event of intense...
Page 29
Service Manual Vacuum pump BLEEDING Humid air left inside the refrigerant circuit can cause compressor (8) Secure INDOOR malfunction. After having connected the indoor and outdoor units, UNIT Refrigerant fluid di rection of fiow ay valve bleed the air and humidity from the refrigerant circuit using a ay valve vacuum pump.
Page 30
Service Manual MULTIU24HP230V1DO 50cm more Space to the cover 30cm or above Space to the cover 30cm or above (Air inlet side) 200cm or above (Air outlet side) MULTIU36HP230V1DO MULTIU42HP230V1DO 50cm or more Space to the cover 30cm or above Space to the cover 200cm or above...
Service Manual 9. Troubleshooting 9.1 Malfunction Indicator ▲ The error code will be displayed on the wired controller and the main board of the outdoor unit The meaning of each error. The indicator display Indoor display Name of malfunction Yellow light Red light Green light Compressor runs...
Service Manual 9.2 Malfunction Checking and Elimination Malfunction display: E6 Communication malfunction Communication malfunction of some indoor units De-energize,check the connection wire of indoor and outdoor unit and the wire of the eletric box is connected correctly Reconnect according to Connected correctly Eliminate the malfunction the wiring diagram...
Page 33
Service Manual All the indoor units appear communication malfunction De-energize,check the connection wire of indoor and outdoor unit and the wire of the eletric box is connected correctly Reconnect according to Eliminate the malfunction Connected correctly? the wiring diagram De-energize, check if the connection wire between the outdoor mainboard and the filter board according to the wiring diagram Reconnect according to...
Page 34
Service Manual Malfunction display: E1 Compressor High Pressure Protection High pressure protection Replace the outdoor Check if the pressure is really high pressure with the Check if pressure switch unit mainboard is abnormal measurement of a manometer Replace pressure switch Refer to Instruction Check if operation mode of indoor unit is Manual of indoor unit...
Page 35
Service Manual Malfunction display: E4 Compressor Exhaust High Temperature Protection Discharge temperature protection Measure if temperature sensor’s Measure if compressor’s discharge Replace relevant discharge resistance value is correct temperature has reached 115℃ temperature sensor System pipeline leaks so complementation is needed. Replace the outdoor Please add refrigerant according to the amount unit mainboard...
Page 36
Service Manual Malfunction display: F2 Failure of Evaporator Temp. Sensor Failure of condenser Temp sensor Check the direction of the plug and Check if the plug of the temperature sensor is correctly socket connected with socket on the mainboard Remove the sensor to check if the resistance value is ok Replace temperature sensor Replace mainboard of the indoor uint Installation and Maintenance...
Page 37
Service Manual Malfunction display: F3 Failure of Outdoor Ambient Sensor Failure of outdoor Ambient sensor Check the direction of the plug Check if the plug of the temperature sensor is correctly and socket connected with socket on the mainboard Remove the sensor to check if the resistance value is ok Replace temperature sensor Replace mainboard of the indoor uint Malfunction display: F5 Failure of Exhaust Temp.
Service Manual 9.3 Maintenance Method for Normal Malfunction 1. Air Conditioner Can't be Started Up Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting Confirm whether it's due to power failure. If yes, No power supply, or poor After energization, operation indicator isn’t bright wait for power recovery.
Page 39
Service Manual 4. ODU Fan Motor Can't Operate Possible causes Discriminating method (air conditioner status) Troubleshooting Connect wires according to wiring diagram to Wrong wire connection, or poor Check the wiring status according to circuit make sure all wiring terminals are connected connection diagram firmly...
Service Manual 10. Exploded View and Parts List MULTIU18HP230V1DO MULTIU24HP230V1DO 12 13 9 10 11 The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
Page 41
Service Manual Part Code Description MULTIU18HP230V1DO MULTIU24HP230V1DO Product code CB228W09400 CB228W09500 Front Grill 016004000006 016004000006 Cabinet 0143543901P 0143543901P Front Side Plate Sub-Assy 017101060007 017101060007 Electrical Heater (Chassis) 7651000413 7651000413 Base Plate Sub-Assy 017000060044P 017000060044P Electromagnetic Valve Sub-assy 030025060020 030025060020 Compressor and Fittings 009001000013 009001000013 Flash Vaporizer Assy...
Page 42
Service Manual MULTIU36HP230V1DO 9 10 11 19 20 The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
Page 43
Service Manual Part Code Description MULTIU36HP230V1DO Product code CB228W09600 Front Grill 016004060003 Drainage Joint 26113009 Front Side Plate Sub-Assy 017101060008P Front Side Plate Sub-Assy 017101060008 Insulated Board (Cover of Electric Box) 20113003 Cabinet 01435007P Axial Flow Fan 10335014 Brushless DC Motor 1570280000409 Motor Support Sub-Assy 017012060043...
Page 44
Service Manual MULTIU42HP230V1DO The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
Page 45
Service Manual Part Code Description MULTIU42HP230V1DO Product code CB228W09700 Front Grill 016004060003 Drainage Joint 26113009 Front Side Plate Sub-Assy 017101060008P Front Side Plate Sub-Assy 017101060008 Insulated Board (Cover of Electric Box) 20113003 Cabinet 01435007P Axial Flow Fan 10335014 Brushless DC Motor 1570280000409 Motor Support Sub-Assy 017012060043...
Service Manual 11. Removal Procedure Warning: Be sure to wait for a minimum of 20 minutes after turning off all power supplies and discharge the refrigerant completely before removal. MULTIU18HP230V1DO MULTIU24HP230V1DO Steps Procedure 1. Remove the handle and valve cover handle Remove the screws connicting the handle with right side plate and then remove the handle.
Page 47
Service Manual Steps Procedure 4.Remove grille and cabinet cabinet Remove the 4 screws connecting the grille and outer case, and then remove the panel grille. grille 5.Remove right side plate and blade right side plate Remove the screws connecting the right side plate with electric box assy, valve support, chassis and condenser side plate, and then remove the right side plate.
Page 48
Service Manual Steps Procedure 7. Remove motor and motor support motor support Remove 4 screws fixing motor,and then remove the motor; Remove 2 screws connecting motor support and chassis, loosen damper block and then remove the motor motor support. 8. Remove clapboard sub-assy clapboard sub-assy Remove 4 screws fixing clapboard sub-assy,and then remove the clapboard sub-assy.
Page 49
Service Manual Steps Procedure 10. Remove flash vaporizer assy flash vaporizer assy Unsolder all spot welds cflash vaporizer assy, and then remove the flash vaporizer assy. 11. Remove electromagnetic valve sub-assy and inhalation tube sub-assy electromagnetic valve sub-assy Unsolder all spot welds electromagnetic valve sub- assy and then remove the electromagnetic valve sub- assy.
Page 50
Service Manual Steps Procedure 13. Remove compressor compressor Remove the 3 foot nuts fixing compressor and then lift the compressor upwards to remove the compressor and damping cushion. Note: Keep the ports of discharge pipe and suction pipe from foreign objects. 14.Remove vapour liquid separator Unsolder spot welds connected with vapour liquid separator, remove 2 foot nuts fixing vapour liquid...
Page 51
Service Manual Steps Procedure 16.Remove left side plate support plate of condenser Remove screws connecting left side plate and support plate of condenser, chassis, and then remove the left side plate. left side plate 17.Remove compressor mounting plate sub-assy Remove the 4 foot nuts fixing compressor mounting plate sub-assy and chassis, to remove the compressor mounting plate sub-assy.
Page 52
Service Manual MULTIU36HP230V1DO MULTIU42HP230V1DO Steps Procedure 1. Remove the handle and valve cover handle Remove the screws connicting the handle with right side plate and then remove the handle and valve cover. valve cover 2. Remove top cover top cover Remove the screws connecting the top cover with outer case, right side plate and left side plate;...
Page 53
Service Manual Steps Procedure 5.Remove right side plate right side plate Remove the screws connecting the right side plate with electric box assy, valve support, chassis and condenser side plate, and then remove the right side plate. 6.Remove grille and cabinet cabinet Remove the 4 screws connecting the grille and outer case, and then remove the panel grille.
Page 54
Service Manual Steps Procedure 8. Remove electric box assy electric box assy 1.Remove the grounding wire screw on the electric box assy and then remove the grounding wire. 2.Disconnect the wiring terminals of reactor, compressor, high and low pressure switch, compressor overload protector, temperature sensor, outdoor fan motor and 4-way valve.
Page 55
Service Manual Steps Procedure 11. Remove oil separator sub-assy oil separator sub-assy Unsolder all spot welds oil separator sub-assy and then remove the oil separator sub-assy. Note:When unsoldering the spot weld, wrap the gas valve and liquid valve with wet cloth completely to avoid damage to valve due to high temperature.
Page 56
Service Manual Steps Procedure 14.Remove connection pipe sub-assy Remove all spot welds connection pipe sub-assy connection pipe sub-assy then remove the connection pipe sub-assy 15.Remove electromagnetic valve sub-assy Remove all spot welds electromagnetic valve sub-assy and then remove the electromagnetic valve sub-assy electromagnetic valve sub-assy 16.
Page 57
Service Manual Steps Procedure 17. Remove valve support valve support Unsolder all spot welds connected with valve support and then remove the valve support. Note:When unsoldering the spot weld, wrap the gas valve and liquid valve with wet cloth completely to avoid damage to valve due to high temperature.
Page 58
Service Manual Steps Procedure 20.Remove supporting board and supporting board sub-assy supporting board Remove the screws connecting the gsupporting board and supporting board sub-assy and remove the gsupporting board and supporting board sub-assy. supporting board sub-assy 21. Remove compressor Remove the 3 foot nuts fixing compressor and then lift compressor the compressor upwards to remove the compressor and damping cushion.
Page 59
Service Manual Steps Procedure 23. Remove middle isolation sheet middle isolation sheet Remove screws connecting middle isolation sheet and support plate of condenser, chassis, and then remove the middle isolation sheet. support plate of condenser 24.Remove left side plate Remove screws connecting left side plate and support plate of condenser, chassis, and then remove the left side plate.
Service Manual Appendix: Appendix 1: Reference Sheet of Celsius and Fahrenheit Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32 Set temperature Fahrenheit Fahrenheit Fahrenheit display Fahrenheit display Fahrenheit display Fahrenheit Celsius (℃) Celsius (℃) Celsius (℃) temperature temperature temperature (℉)...
Page 61
Service Manual Hard mold Note: Expander ● "A" is different according to the diameter, please refer to the sheet below: A(inch) Outer Pipe diameter(inch) Ф0.23 - 0.25 (1/4") 0.051 0.028 Ф9.52 (3/8”) 0.063 0.039 Ф0.37 - 0.5 (1/2”) 0.071 0.039 Ф0.63 (5/8”) 0.095 0.087...
Service Manual Appendix 3: List of Resistance for Temperature Sensor Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor(15K) Temp( C) Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( Resistance(kΩ) 138.1 18.75 3.848 1.071 128.6 17.93 3.711 1.039 121.6 17.14 3.579 1.009 16.39...
Page 63
Service Manual Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K) Temp( C) Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( Resistance(kΩ) 181.4 25.01 5.13 1.427 171.4 23.9 4.948 1.386 162.1 22.85 4.773 1.346 153.3 21.85 4.605 1.307 20.9 4.443 1.269 137.2...
Page 64
Service Manual Resistance Table of Discharge Temperature Sensor for Outdoor(50K) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) 853.5 18.34 4.75 799.8 93.42 17.65 4.61 89.07 16.99 4.47 703.8 84.95 16.36 4.33 660.8 81.05 15.75 4.20 620.8 77.35 15.17 4.08 580.6...
Page 65
Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 E-mail: gree@gree.com.cn www.gree.com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add: Unit 2612,26/F.,Miramar Tower 132 Nathan Road,TST,Kowloon,HK Tel: (852) 31658898 Fax: (852) 31651029 For product improvement, specifications and appearance in this manual are subject to change without prior notice.
Need help?
Do you have a question about the Multi+ Ultra MULTIU18HP230V1DO and is the answer not in the manual?
Questions and answers