Compatibility
UL – Compatible Control Panels
VISTA-32FB
VISTA-32FBT
VISTA-128FBP
VISTA-128FBPT
VISTA-250FBP
VISTA-250BPT
UL – Compatible Receivers
7810iR-ENT
8810iR
MX8000
Ademco 685
7810PC
UL
Compliance
To meet UL864/NFPA, ensure the following:
It must be installed in accordance with NFPA (National Fire Protection Association)
standards 70 and 72.
It must be mounted in the same room and within 20 feet of the fire panel.
Conduit is required for all interconnections between the Fire Panel and communicator.
All equipment used for the IP connection (such as the router, hub, modem, etc.) shall be
listed, must be powered from an un-switched branch circuit, and be provided with
appropriate standby power.
Must be the primary alarm receiver.
Must be the primary alarm receiver.
Can be used for supplemental reporting in ECP mode when connected to
model 7810iR-ENT.
Can be used for supplemental reporting in ECP mode when connected to
model 7810iR-ENT.
Must be the primary alarm receiver
The Automation System must be UL1981 listed.
LTE-CF Installation and Setup Guide
FA1670C (First Alert)
FA1670CT (First Alert)
FA1700C (First Alert)
FA1700CT (First Alert)
4