Register using the TEST / REGISTRATION Switch

Initiate the registration sequence by clicking the TEST / REGISTRATION switch three times.
You can monitor the registration process by viewing the Status Display. The Message (yellow)
LED and the Status (green) LED will blink slowly in unison while registration is in progress.
Once the registration has been completed successfully, the communicator enters normal
operating mode; the Status (green) LED goes out and the Message (yellow) LED is lit to indicate
that the Power On / Reset message is waiting to be sent. This message will appear at the
receiving station as "E339 C08xx", where "xx" is the ECP device address. The description may
read "Trouble – Exp. Mod. Reset". If registration is not validated within 90 seconds, the
communicator times out, and the (green) LED will be lit (solid).
If repeated registration attempts time out, check your Internet connection and RSSI level, and
verify the account information has been entered correctly.

Register using the Programming Tool

The interactive registration feature allows the installer to register the communicator through a
series of keyboard commands on the 7720P Programming Tool. This method of registration lets
the installer monitor the registration process.
Registering ...
Registration
SUCCESS
Possible Errors
Registration BAD
Timed Out
Registration BAD
Pri Sub ID BAD
Registration BAD
Pri ID – Need PIN
Once the installation is complete, press the [Shift] and the up arrow []
key on the 7720P. The registration message is sent and the unit waits
for the acknowledgment.
If this is a new installation and the city, central station, and customer
numbers have been correctly entered, the communicator is registered
and this message is displayed. The communicator is now in full
service and available for alarm reporting to the central station.
Displayed if no response to the registration request is received.
Indicates the city, central station, or customer number for the labeled
account(s) is not accepted. The ID information was either entered
incorrectly, or the central station failed to pre-authorize programmed ID
numbers with AlarmNet customer service.
Displayed if this is a repair / replacement, or an error was made in
programming the Primary account information of the communicator for
an existing account. This prompt appears for 2 seconds. See the
Replacing an existing communicator section below for further displays.