Section 3: Programming the Communicator
PROMPTS
Exit Prog. Mode?
8
(Y/N)_
Comm Path
9
Choice
(2010 IP & Cell)_
NOTE: Account information is provided by the central station administrator. (Prompts 10-12)
Primary City ID
10
(??)_
Primary CS ID
11
(??)
Primary Sub ID
12
(????)
NOTE: Prompts 13 through 17 only appear if the Comm Path Choice is IP, or IP&Cell.
IP Flt Time
13
(60 mins)
NOTE: Refer to table above for
correct default values.
OPTIONS
[Y], [N]
Exits program mode.
Press [N] to go back to Prompt 3.
[ESC]
Press [ESC] to load factory defaults.
Refer to the Exiting Programming Mode paragraph in this section.
2010 IP & Cell
The Comm Path Choice option is a dual-purposed option. The
selection sets the Comm Paths available to the communicator as well
2013 IP
as the supervision interval and fault times necessary to comply with
2013 Cell
the selected edition of the NFPA72 standard.
2013 IP & Cell
The two editions of the standard are 2010 and 2013.
2010 IP
The AlarmNet network must hear at least one message from the
2010 Cell
device during this supervision period; otherwise, AlarmNet notifies the
central station that a communication failure occurred. This interval
cannot be changed.
The settings that correspond to the choices are:
Choice
Supervision Interval
2010 IP & Cell
24 hours
2013 IP
1 hour
2013 Cell
1 hour
2013 IP & Cell
6 hours
2010 IP
5 minutes
2010 Cell
5 minutes
[01-99]
Enter the 2-digit primary city ID, 01-99 (decimal).
[01-FE]
Enter the 2-digit primary central station ID number, 01-FE (HEX).
Enter the 4-digit subscriber account number, 0001-9999 (decimal).
[0001-9999]
This prompt appears only if comm. path includes IP&Cell or IP.
[00-60]
Enter the time delay (1 – 60) in minutes before the
communicator notifies the control there is a communication
path failure over cell. If the panel has an alternate
communication path, a secondary path loss message is sent to
the central station.
DESCRIPTION
IP Fault Time
1 hour
1 hour
- - -
1 hour
5 minutes
- - -
13
Cell Fault Time
1 hour
- - -
1 hour
1 hour
- - -
5 minutes

Hide quick links: