Temperature settings for the operating modes of the Room heating curve in the Automatic heating mode operating mode.
This heating curve can also be adjusted graphically ( operating instructions).
The set flow temperature depends on the measured room temperature. For this, you must install a remote control inside the room.
The heating system is switched off if the room becomes too hot.
Submenu
Settings/
adjustment range
Room temperature setpoint
5...21...50 °C
Room influence /
None
maintenance
According to offset
Maximum / room
maintenance
mode
Room temperature offset
–5...0...5 °C
Standby mode
No/Yes
Heating Limit (Summer from /
No/Yes
Outdoor Setback)
-50...17...50 °C
Manual setback mode
Shortcut keys
Automatic heating mode
Automatic setback mode
Holiday
Table 14 Settings for the operating modes of the Room heating curve
Temperature settings for the operating modes of the Holiday heating curve in the Automatic heating mode operating mode.
This heating curve can also be adjusted graphically ( operating instructions).
Submenu
Settings/
adjustment range
Room temperature setpoint
5...17...50 °C
Room influence /
None
maintenance
According to offset
Maximum / room
maintenance
mode
Room temperature offset
–5...0...5 °C
Standby mode
No/Yes
Heating Limit (Summer from /
No/Yes
Outdoor Setback)
-50...17...50 °C
Table 15 Settings for the operating modes of the Holiday heating curve
Control 8313 – 6720859567 (2017/03)
Explanation
Setting of the required room temperature:
Limits the influence of the room temperature
(room temperature hook-up) on the flow
temperature set value. The value specifies the
highest possible room temperature setback.
This also applies for rooms which are also
supplied by the heating circuit and where no
remote control units are installed.
Adjustment of the temperature differentials
between the actual and set temperature
This adjustment effects a parallel displacement
of the heating curve.
The heating circuit or this function is switched
off.
Selection that determines whether the heating
circuit or a function is to be switched off once a
set outside temperature has been reached.
The heating circuit is switched off when the set
outside temperature is exceeded and switched
back on when it is undercut.
If you tap a shortcut key, the display jumps to
the settings area of the selected operating
mode.
Explanation
Setting of the required room temperature:
Limits the influence of the room temperature
(room temperature hook-up) on the flow
temperature set value. The value specifies the
highest possible room temperature setback.
This also applies for rooms which are also
supplied by the heating circuit and where no
remote control units are installed.
Adjustment of the temperature differentials
between the actual and set temperature
This adjustment effects a parallel displacement
of the heating curve.
The heating circuit or this function is switched
off.
Selection that determines whether the heating
circuit or a function is to be switched off once a
set outside temperature has been reached.
The heating circuit is switched off when the set
outside temperature is exceeded and switched
back on when it is undercut.
Note
Requirements for the setting:
• A Remote Control is selected.
• Room heating system is not selected.
Ensure that the remote control is not exposed to
heat (e.g. lamps, TV sets or other heat sources).
This setting is only recommended if no remote
control has been installed inside the living space.
 Chapter 12.1.3, page 33
The heating circuit is switched off
(summer mode) when the setting is Yes.
The heating circuit is switched off from a set
outside temperature.
You can make separate settings for each
operating mode. For the settings of the setback
types, refer to  Chapter 12.1.2, page 33.
Note
Requirements for the setting:
• A Remote Control is selected.
• Room heating system is not selected.
Ensure that the remote control is not exposed to
heat (e.g. lamps, TV sets or other heat sources).
This setting is only recommended if no remote
control has been installed inside the living space.
 Chapter 12.1.3, page 33
The heating circuit is switched off
(summer mode) when the setting is Yes.
The heating circuit is switched off from a set
outside temperature.
Menu structure