Menu structure
Submenu
Settings/
adjustment range
Actuator runtime
5...120...600 s
Boiler temperature increase
0...5...20 K
No/Yes
DHW priority
Pump blocking protection
Off/On
Overrun time
0...2...60 min
Third party WF control
None
settings
Heating mode/
Setback mode
WF1/2
Heating mode/
Setback mode/
Automatic
WF1/2/3
External fault
display for pump
WF1/2
External fault
display for pump
WF1/2 and
External fault
display for pump
WF1/2 and
external heating/
setback mode
WF1/3 WF1/3
Table 10 Basic settings of heating circuits
22
Explanation
Setting the runtime of the available mixing
valves
Generally, servomotors have a runtime of
120 s.
The flow temperature for the heating circuit is
obtained by adding the increase in boiler
temperature to the calculated/required flow
temperature.
The pumps of all heating circuits are switched
off during the water heating phase.
Setting that determines whether or not a pump/
mixer is to be regularly switched on for short
periods to prevent it from seizing up during
extended downtimes.
Setting that determines how many minutes a
pump should remain switched on once the
switch-on condition no longer exists.
Switching the operating mode of the heating
circuit via an external contact (connecting
terminal WF) at the FM-MM and FM-MW module
Display of faults for a pump
Display of faults for a pump via 1/2 and external
changeover via 1/3.
Note
If the mixing valve constantly oscillates, the
control characteristics can be slowed down by
reducing the operating time of the mixing valve.
If a heating circuit is controlled with a mixing
valve, a higher set value should be set for the heat
source than the normal set value for the heating
circuit.
In heating circuits with mixer, the mixing valve is
moved in the "close" direction (colder).
Not available with the connections of the
boiler circuit.
 Chapter 12.1.2, page 33
Not available with the connections of the
boiler circuit.
Control 8313 – 6720859567 (2017/03)