Sensor Curves; Pressure Drop Values For Outside, Room, Flow And Hot Water Temperature Sensors; Pressure Drop Values For Boiler Water Temperature Sensor And Flue Gas Temperature Sensor With Ems Floor Standing Boiler With Safe Burner Control Unit - Bosch Control 8313 Service Instructions For Contractors

Hide thumbs Also See for Control 8313:
Table of Contents

Advertisement

Appendix
23.2

Sensor curves

DANGER:
Danger to life due to electric shock!
Before opening the device:
▶ Isolate the mains voltage.
▶ Secure against unintentional reconnection.
Checking fault:
▶ Remove sensor terminals.
▶ Check the resistance at the temperature sensor cable ends
using an ohmmeter.
▶ Check the temperature at the temperature sensor with
a thermometer.
The following tables show whether the temperature and pressure
drop value correspond.
The sensor tolerance for all curves is ± 3 % at 25 °C.
23.2.1 Pressure drop values for outside, room, flow and hot water
temperature sensors
Temperature [ °C]
–40
–35
–30
–25
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
110
115
120
Table 32 Pressure drop values of 53xx temperature sensor
50
Resistance []
332100
240000
175200
129300
95893
72228
54889
42069
32506
25313
19860
15693
12486
10000
8060
6536
5331
4372
3605
2989
2490
2084
1753
1480
1258
1070
915
786
677
508
443
387
23.2.2 Pressure drop values for boiler water temperature sensor
and flue gas temperature sensor with EMS floor standing
boiler with SAFe burner control unit
Temperature [ °C]
–10
–5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
Table 33 Pressure drop values for boiler water temperature sensor and
flue gas temperature sensor of EMS floor standing boiler with
SAFe burner control unit
Control 8313 – 6720859567 (2017/03)
Resistance []
50442
39324
30902
24495
19553
15701
12690
10291
8406
6912
5715
4744
3958
3312
2786
2357
2004
1709
1464
1257
1084
939
816
711