Boiler Parameters; Basic Boiler Settings - Bosch Control 8313 Service Instructions For Contractors

Hide thumbs Also See for Control 8313:
Table of Contents

Advertisement

9.3

Boiler parameters

9.3.1

Basic boiler settings

Depending on which boiler type and burner type have been chosen,
special setting options will be displayed.
Submenu
Settings/adjustment
range
Boiler type
None
SAFe
EMS
Hydraulic
Boiler
Heating circuit
Sensor
Heat source
(low loss header)
Heating circuit (Flow)
Boiler circulation pump No/Yes
Modulating pump
No/Yes
Pump control mode
In accordance with
boiler operating
conditions
Off/On
According to output
According to
temperature difference
Temperature difference
1...4...10 K
between boiler and low
loss header
Pump overrun time for
0...60...120 Min
lead boiler
Pump overrun time for
0...60...120 min
slave boiler
0...10 V
Voltage for min. flow
temp
Voltage for max. flow
0...10 V
temp
Boiler temperature
No/Yes
increase at low loss
header
Control 8313 – 6720859567 (2017/03)
Explanation
No boiler available. Control is used as standalone
master control unit with address 0 or as
substation.
The parameters of the SAFe are adopted by the
heat source. A boiler control is not installed in the
heat source.
The parameters of the boiler control the SAFe are
adopted by the heat source in the control unit.
The heating circuit on the central module is used
as boiler circuit.
The heating circuit on the central module is used
as boiler circuit (00).
Setting that specifies whether a boiler circulation
pump is installed.
Setting that specifies the conditions according to
which the pump is controlled
Setting that determines whether the modulating
pump is to be switched on and off via a 0....10 V
signal.
Setting that specifies the conditions according to
which the pump is controlled
Setting of the temperature differential between
temperature sensor in the system flow (FZ) and
boiler water temperature sensor.
To utilise the heat stored in the heat source to the
maximum possible extent, a time must be
specified for which the pump should continue to
operate after the burner has been shut down.
To utilise the heat stored in the heat source to the
maximum possible extent, a time must be
specified for which the pump should continue to
operate after the burner has been shut down.
Specifies the voltage at which the minimum flow
rate occurs.
Specifies the voltage at which the maximum flow
rate occurs.
5 K is added to the desired set value for the boiler
temperature, so that the set value can be reached
quickly and safely.
Note
Standalone as master control unit with address
0. Substation as control unit with address >0
Note selection at menu item Hydraulic.
( Chapter 5, page 8 and chapter 11.2,
page 32)
Note selection at menu item Sensor.
Attention: the SI and external interlock terminal
must be opened!
( Chapter 5, page 8 and chapter 11.2,
page 32)
Boiler/heating circuit 00 with the terminals PK,
SR, FZ ( Chapter 9.4, page 21)
 Chapter 11.1.1, page 32
The control operates within the limits specified
by the SAFe, e.g. maximum boiler temperature.
Digital activation of modulating pump.
Activation: On = 10 V, Off = 0 V
Prerequisite: continuous external power supply
to pump.
▶ Observe pump manufacturer's
specifications.
Change the factory setting only in exceptional
cases.
Change the factory setting only in exceptional
cases.
Observe pump manufacturer's specifications.
Observe pump manufacturer's specifications.