* 1. Based on a standard 4-pole motor for max. applicable motor output.
* 2. Shows deceleration torque for uncoupled motor decelerating from 60 Hz
with the shortest possible deceleration time.
* 3. Minimum permissible load: 5 VDC, 10 mA (as reference value)
* 4. Temperature during shipping (for short period).
* 5. If the wiring distance between Inverter and motor is long, reduce the
Inverter carrier frequency. For details, refer to Reducing Motor Noise or
Leakage Current Using Carrier Frequency Selection (n46) on page 64.
* 6. The ground fault here is one which occurs in the motor wiring while the
motor is running. A ground fault may not be detected in the following
cases.
• A ground fault with low resistance which occurs in motor cables or ter-
minals.
• A ground fault occurs when the power is turned ON.

Standard Specifications (400 V Class)

Voltage Class
Model CIMR-
3-phase
J7∗A
Max. Applicable Motor
*1
Output kW
Inverter
Capacity (kVA)
Rated Output
Current (A)
Max. Output
Voltage (V)
Max. Output
Frequency (Hz)
Rated Input
Voltage and
Frequency
Allowable
Voltage
Fluctuation
Allowable
Frequency
Fluctuation
40P2
40P4
40P7
0.2
0.4
0.75
0.9
1.4
2.6
1.2
1.8
3.4
3-phase, 380 to 460 V (proportional to input voltage)
400 Hz (Programmable)
3-phase, 380 to 460 V, 50/60 Hz
−15% to +10%
±5%
9. Specifications
400 V 3-phase
41P5
42P2
1.5
2.2
3.7
4.2
4.8
5.5
43P0
43P7
3.0
3.7
5.5
6.6
7.2
8.6
109