Voltage Class
Model CIMR-
3-phase
J7∗A
Momentary
Power Loss
Heatsink Over-
heat
Stall Prevention
Level
Cooling Fan
Fault
*6
Ground Fault
Power Charge
Indication
Multi-
function
Input
Multi-
function
Output
Standard Func-
tions
Status
Indica-
tors
Digital
Opera-
tor
Terminals
Wiring Distance
between Inverter
and Motor
Enclosure
Cooling Method
40P2
40P4
Following items are selectable: Not provided (stops if power loss is
15 ms or longer), continuous operation if power loss is approx. 0.5
s or shorter, continuous operation.
Protected by electronic circuit.
Can be set individual levels during acceleration/deceleration, pro-
vided/not provided available during coast to a stop.
Protected by electronic circuit (fan lock detection).
Protected by electronic circuit (rated output current level).
Charge LED is provided.
ON until the DC bus voltage becomes 50 V or less.
Four of the following input signals are selectable: Reverse run (3-
wire sequence), fault reset, external fault (NO/NC contact input),
multi-step speed operation, JOG command, acceleration/deceler-
ation time select, external baseblock (NO/NC contact input),
SPEED SEARCH command, ACCELERATION/DECELERATION
HOLD command, LOCAL/REMOTE selection, communication/
control circuit terminal selection, emergency stop fault, emergency
stop alarm
Following output signals are selectable (1 NO/NC contact output):
Fault, running, zero speed, frequency agree, frequency detection
(output frequency ≤ or ≥ set value), overtorque detection, minor er-
*3
ror, baseblock, operating mode, Inverter run ready, fault retry, UV,
speed search, data output through communication
Full-range automatic torque boost, slip compensation, DC injec-
tion braking current/time at startup/stop frequency reference bias/
gain, frequency reference with built-in potentiometer, constant
copy, [MEMOBUS communications (RS-485/422, max.19.2K bps)
(optional)]
RUN and ALARM provided as standard indicators
Provided for monitor frequency reference, output frequency, out-
put current
Main circuit: screw terminals
Control circuit: plug-in screw terminal
*5
100 m or less
Open chassis IP20
Cooling fan is provided for the following models:
400 V, 1.5 kW or larger Inverters (3-phase)
Other models are self-cooling.
9. Specifications
400 V 3-phase
40P7
41P5
42P2
43P0
43P7