10 Configuration
Auto restart
Auto restart
When power returns after a power supply failure, the auto restart
function reapplies the remote controller settings at the time of the
power failure. Therefore, it is recommended to always enable the
function.
If the preferential kWh rate power supply is of the type that power
supply is interrupted, always enable the auto restart function.
Continuous indoor unit control can be guaranteed independent of the
preferential kWh rate power supply status, by connecting the indoor
unit to a normal kWh rate power supply.
#
Code
[9.E]
[3-00]
Auto restart:
▪ 0: Manual
▪ 1: Automatic
Disable protections
INFORMATION
The software is equipped with an "installer-on-site" mode
([9.G]: Disable
protections), that disables automatic
operation by the unit. At first installation, setting Disable
protections is by default set to Yes, meaning automatic
operation is disabled. All protective functions are then
disabled. To enable automatic operation and the protective
functions, set Disable protections to No.
36 hours after the first power-on, the unit will automatically
set Disable protections to No, ending "installer-on-site"
mode and enabling the protective functions. If –  after first
installation  – the installer returns to the site, the installer
has to set manually Disable protections to Yes.
#
Code
[9.G]
N/A
Disable protections
▪ 0: No
▪ 1: Yes
Brine freezing temperature
Brine freezing temperature
Depending on the type and concentration of the anti-freeze in the
brine system, the freezing temperature will differ. The following
parameters set the units freeze up prevention limit temperature. To
allow
for
temperature
measurement
concentration MUST resist to a lower temperature than the defined
setting.
General rule: the units freeze up prevention limit temperature MUST
be 10°C lower than the minimum possible brine inlet temperature for
the unit.
Example: When the minimum possible brine inlet temperature in a
certain application is –2°C, then the unit freeze up prevention limit
temperature MUST be set to –12°C or lower. Result will be that the
brine mixture may NOT freeze above that temperature. To prevent
freezing of the unit, check the type and concentration of the brine
carefully.
Installer reference guide
84
Description
Description
tolerances,
the
brine
#
Code
[9.M]
[A‑04]
Brine freezing temperature
▪ 0: 2°C
▪ 1: –2°C
▪ 2: –4°C
▪ 3: –6°C
▪ 4: –9°C
▪ 5: –12°C
▪ 6: –15°C
▪ 7: –18°C
NOTICE
The Brine
freezing
modified and read out in [9.M].
After changing the setting in [9.M] or in the field settings
overview [9.I], wait 10 seconds before restarting the unit
via the user interface to ensure that the setting is saved in
the memory correctly.
This setting can ONLY be modified if the communication
between hydro module and compressor module is present.
The
communication
compressor module is NOT guaranteed and/or applicable
if:
▪ error "U4" appears on the user interface,
▪ the heat pump module is connected to preferential kWh
rate power supply where power supply is interrupted
and preferential kWh rate power supply is activated.
Overview field settings
All settings can be done using the menu structure. If for any reason it
is required to change a setting using the overview settings, then the
overview settings can be accessed in the field settings overview [9.I].
setting" [ 4  55].
See
"To modify an overview

10.5.10 Operation

In the operation menu, you can separately enable or disable
functionalities of the unit.
#
Code
Room
[C.1]
N/A
▪ 0: Off
▪ 1: On
[C.2]
N/A
Space heating/cooling
▪ 0: Off
▪ 1: On
[C.3]
N/A
Tank
▪ 0: Off
▪ 1: On
Description
temperature setting can be
between
hydro
module
and
Description
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569820-1A – 2019.09