10 Configuration
CAUTION
If there are 2 zones and the emitter types are wrongly
configured, water of high temperature can be sent towards
a low temperature emitter (underfloor heating). To avoid
this:
▪ Install an aquastat/thermostatic valve to avoid too high
temperatures towards a low temperature emitter.
▪ Make sure you set the emitter types for the main zone
[2.7] and for the additional zone [3.7] correctly in
accordance with the connected emitter.
Pump operation mode
When the space heating/cooling operation is OFF, the pump is
always OFF. When space heating/cooling operation is ON, you have
the choice between these operation modes:
#
Code
[4.5]
[F–0D]
Pump operation mode:
▪ 0
operation, regardless of thermo ON or
OFF condition. Remark: Continuous
pump operation requires more energy
than
operation.
b
b
a Space heating/cooling control
b Off
c On
d Pump operation
▪ 1 Sample: The pump is ON when there
[4.5]
[F-0D]
is heating or cooling demand as the
leaving water temperature has not yet
reached the desired temperature yet.
When thermo OFF condition occurs,
the pump runs every 3 minutes to
check the water temperature and
demand
necessary. Remark: Sample is ONLY
available in leaving water temperature
control.
a
b
d
g
b
a Space heating/cooling control
b Off
c On
d LWT temperature
e Actual
f Desired
g Pump operation
Installer reference guide
72
Description
Continuous:
Continuous
pump
sample
or
request
pump
a
c
c
d
heating
or
cooling
c
e
f
c
#
Code
[4.5]
[F-0D]
Unit type
In this part of the menu it can be read out which type of unit is used:
#
Code
[4.6]
[E‑02]
Pump limitation
Pump speed limitation [9‑0D] defines the maximum pump speed. In
normal conditions, the default setting should NOT be modified. The
pump speed limitation will be overruled when the flow rate is in the
range of the minimum flow (error 7H).
#
Code
[4.7]
[9-0D]
if
The maximum values depend on the unit type:
[9-0D]=0
a (kPa)
b (l/min)
Description
▪ 2 Request: Pump operation based on
request. Example:
Using a room
thermostat and thermostat creates
thermo ON/OFF condition. Remark:
NOT
available
in
leaving
temperature control.
a
b
c
d
c
b
e
b
c
a Space heating/cooling control
b Off
c On
d Heating demand (by external room
thermostat or room thermostat)
e Pump operation
Description
Unit type:
▪ 0 Reversible
▪ 1 Heating only
Description
Pump limitation:
▪ 0: No limitation
▪ 1~4: General limitation. There is
limitation
in
all
conditions.
required delta T control and comfort
are NOT guaranteed.
▪ 5~8: Limitation when no actuators.
When there is no heating output, the
pump speed limitation is applicable.
When there is heating output, the
pump speed is only determined by
delta  T in relation to the required
capacity. With this limitation range,
delta  T is possible and the comfort is
guaranteed.
[9-0D]=5
a (kPa)
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569820-1A – 2019.09
water
The
b (l/min)