FBII XL-20 Hookup And Installation Instructions page 69

Hardwired/wireless system
Hide thumbs Also See for XL-20:
Table of Contents

Advertisement

XL-20 Hookup and Installation Instructions
transmits at a much greater speed than the conventional pulse formats, since it uses DTMF
(touch-tones) instead of pulses to transmit the data, and it always sends a parity digit. Its
main advantage over all the other formats is its large number of Event codes (see tables
below) with the ability to pinpoint an event (Alarm, Trouble, Bypass, Restore, etc.) to a
specific sensor (up to 32 points in this system) and to report Openings/Closings for many
users (up to 15 users in this system).
For some Reporting codes, the first of the two programmable digits determines the PID
Event code to be transmitted. Other reporting codes transmit a dedicated PID Event code
regardless of the digit programmed in the first location. In both cases, if transmissions are
not desired, then program AA in locations 1 and 2. Refer to the following tables to select the
PID Event codes to be transmitted.
BURGLARY ZONE TYPES
Digit
0
1
2
3
4
5
6
7
8
9
A
B
C
D
FIRE ZONE TYPES
Digit
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
A–4
EVENT
ENGLISH OUTPUT
CODE
AT CS RECEIVER
122
Silent Panic
123
Audible Panic
130
Burglary
131
Perimeter
132
Interior
133
24-Hour Alarm
134
Entry/Exit
135
Day/Night
136
Outdoor
137
Tamper
140
General Alarm
144
Sensor Tamper
155
Foil Break
156
Day Trouble
EVENT
ENGLISH OUTPUT
CODE
AT CS RECEIVER
110
Fire Alarm
111
Smoke
112
Combustion
113
Water Flow
114
Heat
115
Pull Station
116
Duct
117
Flame
140
General Alarm
150
24-Hour Non-Burg
158
High Temperature
159
Low Temperature
200
Fire Supervisory
201
Low H2O Pressure
202
Low CO2
203
Gate Valve Sensor
24-Hour ALARM TYPES
EVENT
ENGLISH OUTPUT
Digit
CODE,
AT CS RECEIVER
0
100
Medical
1
101
Pendant Transmitter
2
120
Panic Alarm
3
122
Silent Panic
4
123
Audible Panic
5
130
Burglary
6
133
24-Hour Alarm
7
135
Day/Night
8
137
Tamper
9
140
General Alarm
A
150
24-Hour Non-Burg
B
151
Gas Detected
C
152
Refrigeration
D
153
Loss of Heat
E
154
Water Leakage
F
155
Foil Break
24-Hour TROUBLE TYPES
EVENT
ENGLISH OUTPUT
Digit
CODE
AT CS RECEIVER
0
100
Medical
1
122
Silent Panic
2
123
Audible Panic
3
137
Tamper
4
150
24-Hour Non-Burg
5
153
Loss of Heat
6
155
Foil Break
7
156
Day Trouble
8
158
High Temperature
9
159
Low Temperature
A
300
System Trouble
B
301
AC Loss
C
302
Low System Battery
D
310
Ground Fault
E
373
Fire Trouble
F
380
Sensor Trouble

Advertisement