Question 06, L4
Fire Bell Cutoff
Using the table in question 06 location 3 to determine valid choices, enter the desired bell
cutoff time for Fire conditions in 3-minute intervals (for example, 3 = 9 minutes). The valid
range of input is 1 - F, with F indicating an infinite fire bell cutoff. For UL installations, the
minimum fire bell cutoff time shall be 6 minutes.
QUESTION 07
MISCELLANEOUS SYSTEM OPTIONS
There are 4 locations (L1-L4) within this question, which defines various system timing
options, as follows:
Question 07 L1
Entry Delay 2
Using the table in question 6 location 1 to determine valid choices, enter the desired entry
delay time for zones 4-8. If zones 4-8 are delay zones, then they follow entry delay 2.
For UL applications, the maximum entry delay shall not exceed 45 seconds for household
applications or 15 seconds for commercial burglary applications.
Question 07, L2
Remote Communications Ring Count
Selecting from the choices below, enter a digit in location L2.
BURGLARY & FIRE BELL
Digit
TIMEOUTS
1
3 MINUTES
2
6 MINUTES
3
9 MINUTES
4
12 MINUTES
5
15 MINUTES
6
18 MINUTES
7
21 MINUTES
8
24 MINUTES
9
27 MINUTES
A
30 MINUTES
B
33 MINUTES
C
36 MINUTES
D
39 MINUTES
E
42 MINUTES
F
INFINITE
REMOTE COMMUNICATIONS
Digit
RING COUNT
0
NONE (REMOTE COMM. DISABLED)
1
1 RING
2
2 RINGS
3
3 RINGS
4
4 RINGS
5
5 RINGS
6
6 RINGS
7
7 RINGS
8
8 RINGS
9
9 RINGS
A
10 RINGS
B
11 RINGS
C
12 RINGS
D
13 RINGS
E
14 RINGS
F
15 RINGS
Section 9 - System Programming
Default = F
DEFAULT = 2C06
Default = 2
Default = C
9–9