FBII XL-20 Hookup And Installation Instructions page 13

Hardwired/wireless system
Hide thumbs Also See for XL-20:
Table of Contents

Advertisement

XL-20 Hookup and Installation Instructions
7(-) & 8(+)
5(-) & 8(+)
9(+) & 10(-)
11(+) & 10(-)
12(+) & 13(-)
14(+) & 13(-)
RF RECEIVER
INTERFACE
2–4
SMOKE DETECTOR POWER OR TRIGGER OUTPUT:
SMOKE DETECTOR POWER:
smoke detectors only. Approximately 50mA of current is available at
these terminals for powering all detectors and an EOL relay FBII Model
620. For UL installations, see wiring diagram for hookup.
These terminals adhere to the fire verification and reset logic, which is
explained in the zone types section of this manual. You can reset the
smoke detector power manually by entering a valid user code after
clearing alarm memory or by using the asterisk (*) key.
These terminals can be used for a trigger output. See
TRIGGER OUTPUT:
programming question 28, locations 1 and 2 for valid trigger types.
REGULATED POWER (11.5 - 13.1VDC):
The total regulated output power for motion detectors and other external
devices is 500mA at 11.8 - 12.5V for residential applications, or 12.0 -
12.5V for commercial applications, with less than 100 mVPP ripple. The
total regulated output capacity of the XL-20 includes the power available
from these terminals (8 & 5) as well as the power used by the keypads
and smoke detectors. Therefore, to determine the total power available
from these terminals, subtract the power consumed by the keypads and
smoke detectors.
ZONE INFORMATION (HARDWIRED ZONES):
Zone 1 (Requires 2.2K EOL resistor)
Zone 2 (Requires 2.2K EOL resistor)
Zone 3 (Requires 2.2K EOL resistor)
Zone 4* (Requires 2.2K EOL resistor)
Normally-closed devices may be wired in series; normally open devices
may be wired in parallel. A 2.2k-ohm end-of-line resistor must be
installed on all zones. (Refer to the wiring diagram.) The standard loop
response time is 280 ms on all zones. The factory default values for each
zone are listed in the table above; however, any zone can be programmed
for the following types: Delay, Perimeter, Interior, Fire, 24-Hr. Alarm, or
24-Hr. Trouble. Further explanation of the zone types can be found in the
System Programming section of this manual.
NOTE: Loop response is defined as the minimum time required for a
fault to trip a zone.
* If Pool Zone option is enabled, see the "Pool Zone Connections"
paragraph below for zone 4 usage.
ZONE INFORMATION (WIRELESS ZONES):
Zone 5 (Compatible RF Devices)
Zone 6 (Compatible RF Devices)
Zone 7 (Compatible RF Devices)
Zone 8 (Compatible RF Devices)
Wireless zones can be enabled in program question #26, locations 1 and 2.
All 8 zones can be wireless; or up to 4 zones can be hardwired and the
remaining ones wireless. Compatible ADEMCO 5800 Series wireless
devices must be used.
This system will accept 9.5 - 12VDC 4-wire
[Default = DELAY]
[Default = INTERIOR]
[Default = PERIMETER]
[Default = PERIMETER]
[Default = PERIMETER]
[Default = PERIMETER]
[Default = PERIMETER]
[Default = PERIMETER]

Advertisement

Table of Contents
loading

Table of Contents