Assembly Instructions; Assembly Radiant And Burner Kit - Schwank infraSchwank D Series Technical Manual

Radiant tube heater
Table of Contents

Advertisement

infraSchwank D / calorSchwank D shape U

9 Assembly instructions

Assembly radiant and burner kit

Assembly
infraSchwank D / calorSchwank D 15U
Tools you need

• hexagonal wrench or ratchet
[width: 10, 13]
• socket wrench [width: 7 and 8]
Note before mounting
 Note the distance measure of suspension
brackets.
 Flanges are mounted with flange packing
[each 4 screws/washers/lock washers/nuts M8].
 Start mounting the heater at the turnaround
box connection.
 Turn welding line of the tubes to the side.
 Tube with turbulator [with paint mark] has to be
mounted behind the turnaround box [flow
direction]. The paint mark showing to the
turnaround box!
 Tube bars have to be fixed by nuts/lock
washers/3D-washers M8 on the suspension
bracket.
 First the reflector will be fixed on the U-bend
connection by screws/self-locking nuts/lock
washers/3D-washers M5. For insulated reflectors
[calorSchwank D] the reflector end with notch
on sides shows to the turnaround box.
 The other reflector ending will be shoved under
the clip of the suspension brackets. Reflector
and front plate have to be fixed by screws/self-
locking nuts/lock washers/3D-washers M5.
 Mounting of burner unit with valve on the top.
Fig. 17: Mounting of infraSchwank D / calorSchwank D 15U
[all dimensions in mm]
24
Flue gas connection [Type B23, C]
Flexible stainless steel pipe with connector
flange has to be mounted at the end of the
tube with a gasket.
Accessory
for indirect flue into the room [Type A]
Flue gas diverter code-no. 126 7018 0 or
flue gas adapter code-no. 126 7035 0
Note that the flue gas diverter or adapter is
mounted at the end of the tube.
Note that the flue gas diverter is mounted in a
position so that the flue gas is diverted from the
burner.