Schwank infraSchwank D Series Technical Manual page 12

Radiant tube heater
Table of Contents

Advertisement

infraSchwank D / calorSchwank D shape U
Flexible exhaust system infraSchwank D / calorSchwank D 15-60U [roof terminal]
- verison aluminium -
The stainless flexible pipe [exhaust line]
must be installed uncut. Make sure that
there is no sink in the pipe.
Connection stainless steel flexible pipe
to aluminium tube must be glued with
heat-resistant sealing material and
locked by means of self-tapping screws.
All socket connections on the exhaust
and air line must be locked by means of
self tapping screws.
The 90° elbow at the sucking fan side is
to mount with the opening on the top.

System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
CE 0432-CPD-217915, System 0.2 / 0.5
[Muelink&Grol]
Following components are required for mounting
the roof terminal aluminum version
[Distance heater- terminal approx. 1.5 m]:
Roof terminal M&G: Article no. 12221770
Testing set C 15-20kW: Article no. 12676660
Testing set 30-60kW: Article no. 12676750
Dimension flat roof sockets
Article no.
Flat version –
Article no.
High version –
Fig. 9: Position of control points [roof terminal], version aluminium
12
12201087
Transition stainless steel
flexible pipe on
12201788
aluminum pipe
Exhaust gas:
Stainless steel flexible pipe
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 40 mm
- double-wall exhaust pipe + roof
terminal: 0 mm
The roof terminal is slide in from above

into the roof socket. in from above into
the roof socket. The fixing inside the
building takes place via a clamp to the
building ceiling.
Control points
Combustion air:
15-20U: aluminium
flexible pipe
30-60U: stainless steel
flexible pipe