Assembly
infraSchwank D / calorSchwank D 60U
Tools you need
• hexagonal wrench or ratchet
[width: 10, 13]
• socket wrench [width: 7 and 8]
• hand rivet tool
Note before mounting
Note the distance measures of suspension
brackets.
Flanges are mounted with flange packing
[each 4 screws/washers/lock washers/nuts M8].
Stainless steel tube L=5950 mm is the first tube
after the burner unit. Tubes with same length
are mounted parallel.
Start mounting the heater at the turnaround
box connection.
Turn welding line of the tubes to the side.
Tube bars have to be fixed by nuts/3D-
washers/lock washers M8 on the suspension
brackets.
Bracket bars have to be fixed by
screws/washers/ lock washers/nuts M8 on all
suspension brackets.
Start the reflector mounting at the turnaround
box connection. Reflector will be fixed on the
turnaround box connection by screws/self-
locking nuts/lock washers/3D-washers M5. For
insulated reflectors [calorSchwank D] the
reflector end with notch on sides shows to the
turnaround box.
The other reflector endings lie on top to each
other on the bracket bars.
The short reflector L=1500 mm is mounted in the
middle of the heater. Note the distance
measure of suspension brackets.
The intermediate reflectors have to be fixed
with the both front reflectors [each reflector
with 2 middle reflectors]. At the end of the main
reflector sheet the middle reflector is riveted by
2 stainless steel rivets [this reflectors have
already bores to accept the rivets]. At the other
end an additional short angled bracket either
shape V is fixed at the centre of the main
reflector.
Reflectors and bracket bar will be jointly fixed
by 3x M 5 screws and self-locking nuts.
Front plate, reflector and bracket bar have to
be fixed by screws/self-locking nuts/lock
washers/3D-washers M5.
Mounting of burner unit with valve on the top.
Flue gas connection [Type B23, C]
Flexible stainless steel pipe with connector
flange has to be mounted at the end of the
tube with a gasket.
infraSchwank D / calorSchwank D shape U
Accessory
for indirect flue into the room [Type A]
Flue gas diverter code-no. 126 7018 0 or
flue gas adapter code-no. 126 7035 0
Note that the flue gas diverter or adapter is
mounted at the end of the tube.
Note that the flue gas diverter is mounted in a
position so that the flue gas is diverted from the
burner.
Fig. 21: Mounting of infraSchwank D / calorSchwank D 60U
[all dimensions in mm]
29