Schwank infraSchwank D Series Technical Manual page 14

Radiant tube heater
Table of Contents

Advertisement

infraSchwank D / calorSchwank D shape U
Flexible exhaust system [roof terminal]
infraSchwank D / calorSchwank D 15- 60U
- version stainless steel -
Install stainless steel flexible pipe
without sink.
Join parts of the roof terminal strongly
together by compression and using
of jointing and sealing paste
[e.g. Ceramax]!
All joints inside the building tighten
securely with clamp fittings!
The 90° elbow at the sucking fan side is
to mount with the opening on the top.

The roof terminal is fastened with screws
by means of the integrated flange plate
on the building ceiling. The flange plate
supports and secures the roof terminal.
Following components are required for mounting
the roof terminal stainless steel version
[Distance heater- terminal approx. 1.5 m]:
Stainless steel exhaust system roof terminal
DN 100/160 Article no. 12202080
Fig. 11: Position of control points 15 – 60U [roof terminal], version stainless steel
14
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 80 mm
- double-wall exhaust pipe
+ roof terminal: 0 mm

System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
Future ew
Future ew-flex CE 0036-CPR-00055-207 /
Future dw
[Schräder]
CE 0432-CPR-00055-209 /
CE 0432- CPR-00055-301