Flexible exhaust system deltaSchwank [wall terminal]
infraSchwank D / calorSchwank D 15-60U
- version stainless steel -
Install stainless steel flexible pipe
without sink.
Join parts of the roof terminal strongly
together by compression and using
of jointing and sealing paste
[e.g. Ceramax]!
All joints inside the building tighten
securely with clamp fittings!
The 90° elbow at the sucking fan side is to
mount with the opening on the top.
The wall terminal is mounted with a
small gradient to outside to prevent
intrusion of driving rain.

The wall terminal is fastened to the
building wall with screws by means of
the integrated flange plate. The flange
plate supports and secures the wall
terminal.
Fig. 10: Position of control points 15 – 60U [wall terminal], version stainless steel
infraSchwank D / calorSchwank D shape U
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 80 mm
- double-wall exhaust pipe
+ wall terminal: 0 mm

System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
Future ew
Future ew-flex CE 0036-CPR-00055-207 /
Future dw
[Schräder]
Following components are required for mounting
the wall terminal stainless steel version
[Distance heater- terminal approx. 1.5 m]:
Stainless steel exhaust system wall terminal
DN 100/160
CE 0432-CPR-00055-209 /
CE 0432- CPR-00055-301
Article no. 12202220
: