Flexible exhaust system deltaSchwank [wall terminal]
infraSchwank D / calorSchwank D 15-60U
- version stainless steel -
Install stainless steel flexible pipe
without sink.
Join parts of the roof terminal strongly
together by compression and using
of jointing and sealing paste
[e.g. Ceramax]!
All joints inside the building tighten
securely with clamp fittings!
The 90° elbow at the sucking fan side is to
mount with the opening on the top.
The wall terminal is mounted with a
small gradient to outside to prevent
intrusion of driving rain.
The wall terminal is fastened to the
building wall with screws by means of
the integrated flange plate. The flange
plate supports and secures the wall
terminal.
Fig. 10: Position of control points 15 – 60U [wall terminal], version stainless steel
infraSchwank D / calorSchwank D shape U
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 80 mm
- double-wall exhaust pipe
+ wall terminal: 0 mm
System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
Future ew
Future ew-flex CE 0036-CPR-00055-207 /
Future dw
[Schräder]
Following components are required for mounting
the wall terminal stainless steel version
[Distance heater- terminal approx. 1.5 m]:
Stainless steel exhaust system wall terminal
DN 100/160
CE 0432-CPR-00055-209 /
CE 0432- CPR-00055-301
Article no. 12202220
: