infraSchwank D / calorSchwank D shape U
Assembly burner kit exhaust gas
collection system
Conversion kit burner kit single heater to
exhaust gas collection system
Article No. 126999 9
Conversion kit includes the components for
converting the burner kit for use in an exhaust gas
collection system and provides the parts for
connecting the exhaust side.
The following steps are required to convert the
burner kit.
 Remove the self-tapping screws of the air
pressure switch [APS] fastening and fasten the
2/2-way valve bracket together with APS with
added longer self-tapping screws [Fig. 24].
 Fix 2/2-way valve with added 2x M4 screws to
the bracket. Connection bushing with hole
0.6 mm must be showing to the right [Fig. 25
and 26].
 Remove the measuring pipe differential
pressure [- contact] between venturi fan and
APS.
 Now fit two new measuring pipes between
venturi fan / 2-2-way valve / APS[- contact].
Making sure that the measuring pipe with
damping nozzle  0.6mm is mounted on the
right side.
Attention: Do not cover the bore of the
connecting bushing [Fig. 26]!
 Place additional cable gland on right housing
wall IC 4000/1.
 Connect connection cable 2/2-way valve [L, N]
to the existing plug-in terminals within IC 4000/1
[type: WAGO, fan voltage output], clamp PE on
PE GV 2, connect plug with 2/2-way valve and
secure with screws.
 Close the housing lid IC 4000/1.
 After burner kit conversion the exhaust
components must be assembled [adaptor and
damper]. Adaptor is mounted with the seal on
the loose flange of the last radiant tube
[Fig. 28].
30
Fig. 23 : Scope of delivery conversion kit
Fig. 24: Fit bracket for APS
Fig. 25 : Assembled APS on bracket
Fig. 26: Hole position connection bushing on right side