Connection Of The Pipes - Kessel Aqualift F Duo/XXL SPF 550 KE Installation, Operating And Maintenance Instructions

Lifting station for wastewater with and without faeces for free-standing installation in rooms protected from frost
Table of Contents

Advertisement

The delivery includes the following parts (see section 2.2):
- Sump with all mounted parts
- Electrical switchgear
- Accessories
IMPORTANT:
The electrical switchgear must be stored in a frost-free
and dry place. If the system is not connected electrical-
ly during installation, the switchgear must be stored pro-
perly in the meantime.
CAUTION:
Risk due to heavy weights. The lifting systems each weigh
approx. 45 kg (single systems) and approx. 84 kg (double sy-
stem). The parts may only be lifted and mounted taking
great care and whilst wearing the correct equipment. If the
system is dropped irreparable damage may be caused to
the system parts (e.g. pump) or the entire system. This da-
mage is not covered by the warranty.
INSTALLATION SITE:
The KESSEL Aqualift
®
free-standing installation in frost-protected rooms. The
associated switchgear needs to be installed in a dry room
protected from flooding and frost..
4. Installation and assembly
F lifting system is designed for
9
4.1 Assembly of the sumps
To allow assembly, maintenance and servicing work to be
carried out on the lifting systems easily, they always need
to be installed so that the lifting system can be easily ac-
cessed and that there is at least a free space of 60 cm aro-
und the system as stipulated in EN 12056 (all round and on
top).
The system must installed horizontally in an appropriate po-
sition in the room on sound absorbing material (available
from KESSEL as an accessory). The lifting system must be
connected to the ground using the supplied brackets, scr-
ews and wall plugs to prevent it from slipping or turning.

4.2 2 Connection of the pipes

All pipes must be installed so that they can empty on their
own. All pipe connections must be designed to be flexible
and sound-damping.
A standard plastic sleeve can be pushed over the pipes
Connections to the drilling surfaces on the side (for supply line
or manual diaphragm pump) by drilling with the hole saw*, ins-
ertion of the matching greased seal* and pushing over a plastic
pipe (see Fig. A)
Tank lifting system
Abb. A
* KESSEL accessory
Pipe opening seal
Pipe connection