General; Application Scope - Kessel Aqualift F Duo/XXL SPF 550 KE Installation, Operating And Maintenance Instructions

Lifting station for wastewater with and without faeces for free-standing installation in rooms protected from frost
Table of Contents

Advertisement

2.1 Application scope

The lifting systems pump the wastewater (with and without
faeces) that is collected below the drain and local back-up
level into the sewers fully automatically in compliance with
the stipulations of EN 12056. They may only be used for
household wastewater, for example from detached homes
and apartment buildings, commercial operations, hotels and
restaurants, shops, hospitals, schools or other similar cases.
If the incoming flow to the lifting system may not be inter-
rupted during normal operation, the lifting system also
needs to be equipped with a second pumping device with
the same output level that can switch on automatically if re-
quired (double instead of single system).
2.2 Description of the Aqualift F Duo XXL system
➀ Intake line DN 150
➁ Pressure connection DN 100
➂ Ventilation DN 100
➃ Two wastewater pumps each with a 5 m connection line
➄ Sump made of polyethylene
5

2. General

The KESSEL Aqualift
standing installation in frost-protected rooms. The associa-
ted switchgear needs to be installed in a dry room protec-
ted from flooding and frost. The pressure lines must be de-
signed to be at least DN 80, the ventilation lines at least DN
50. Abrasive media must be kept away from the pump im-
peller.
The systems are suitable for permanent wastewater tempe-
ratures of up to 35°C. Brief (up to 10 minutes) incoming tem-
peratures of maximum 60°C are allowed.
1993 mm
1092 mm
1923 mm
➅ Cleaning aperture
➆ Blocking device
➇ Check valve
®
F lifting system is designed for free-
391 mm