Power-Up And Led Statuses With Transceiver 21-219 - ABB Relion 670 Series Application Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 5
Communication set-up
Every switch position for clock selection is represented by the four LEDs (1, 2, 4 and 8) on the
front panel as shown in Table
value for each switch position.
Table 26: LEDs indicating clock synchronization configuration by the rotary switch
LED 1
X
5.6.5
Power-up and LED statuses with transceiver 21–219
To power up transceiver 21–219, connect the power cord to the transceiver, and then connect
the other end of the cord to mains.
IEC07000246 V1 EN-US
Figure 84: Channel LED indicators
1
2
LED name
LA
RA
ST
82
26
(X indicates a lit LED). The LEDs form a corresponding binary-
LED 2
LED 3
Status LEDs for Channel 0
Status LEDs for Channel 1
LED function
Local Alarm. Red LED indicates that transceiver 21-219 has detected a fault condition in
the C37.94 protocol (LOS = Loss Of Signal). The Yellow Alarm bit is set in the outgoing
C37.94 protocol.
The red LED is lit when transceiver 21-219 has detected an error. The indication has a
memory function. When the local error is no longer present, the LED blinks until the Reset
button is pressed.
Remote Alarm. Red LED indicates that the remote unit has detected a fault condition, and
has set the Yellow Alarm bit in the C37.94 protocol.
The red LED is lit when the fibre-optic link has detected an error. The indication has a
memory function. When the remote error is no longer present, the LED blinks until the
Reset button is pressed.
Status. The red LED is lit when transceiver 21–219 has set outgoing data on fibre-to-AIS
condition.
© Copyright 2017 ABB. All rights reserved
LED 4
Function
(0H) External clock selected (slave mode)
(1H) Internal clock selected (master mode)