Section 5
Communication set-up
Test 2 to Test n: loop back RX+ to TX+ and RX- to TX-. Loop back, one-by-one, in respective
interface in the communication network. Check that the communication status is OK for each
interface point on the local HMI. If no fault is found, Test 1 and Test 2 should be repeated in
reverse order from the remote end.
90
When loop-back testing is finished, remember to restore the original terminal
numbers. Having the same terminal number at both ends can cause an
unwanted trip. If the terminal was set to Test mode, check that the local trip is
reset before leaving the Test mode