Configuration Of Binary Inputs And Outputs; Configuration Of Binary Inputs And Outputs Via Act - ABB Relion 670 Series Application Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 382-UEN E
4.8.2

Configuration of binary inputs and outputs

4.8.2.1

Configuration of binary inputs and outputs via ACT

LDCM hardware channels can be connected via ACT by right-clicking on the chosen connection
point, and then selecting Connect/Hardware Channel (see Figure 46).
IEC10000241 V1 EN-US
Figure 46: Configuration of binary inputs and outputs via ACT
The following can be done in the Hardware Channel Allocation dialog:
Hardware Module selection
Hardware Channel selection
User Defined Name for the channel
IEC10000242 V1 EN-US
Figure 47: Hardware Channel Allocation dialog
Communication set-up, 670/650 series
Application Guide
Signals are available in the Signal Matrix Tool (SMT) and as hardware channels
in the Application Configuration Tool (ACT).
If an installed LDCM is not used, it should be removed or set to binary mode
without any connections, or the
Blocked . Otherwise parallel LDCMs may get blocked.
© Copyright 2017 ABB. All rights reserved
Analog and binary signal transfer for line differential protection
ChannelMode parameter should be set to
IEC10000242-1-en.vsdx
Section 4
GUID-89D944D1-DD6C-4666-8AA6-38FE5F366095 v1
GUID-0918C53D-F755-4FA1-BB3C-F672AFC6A7D2 v1
GUID-7102E264-F540-434C-96BA-47E72DA665B2 v1
45

Advertisement