Flush Mounting The Ied With A Protection Cover - ABB 620 series ANSI Installation Manual

Hide thumbs Also See for 620 series ANSI:
Table of Contents

Advertisement

1MAC457436-IB B
4.3.6
620 series ANSI
Installation Manual
C
GUID-7BF7BB39-F24C-4D0A-8279-DED6D32B03F5 V1 EN
Figure 19:
Wall-mounted IED
A 10.20 inches (259 mm)
B 12.52 inches (318 mm)
C 7.32 inches (186 mm)
Leave enough slack to wires and cables to allow installation movement.

Flush mounting the IED with a protection cover

A mounting kit is needed for flush mounting the IED with a protection cover. The
mounting kit includes detailed mounting instructions and the protection cover.
Installation requirements:
Panel cut-out of 9.76 x 6.38 inches (248 x 162 mm)
Depth behind the panel 6.69 inches (170 mm)
A
B
Section 4
Mounting
31