1MRK 505 382-UEN E
IEC10000247 V1 EN-US
Figure 50: Tab selection in SMT for binary input and output configuration
Figure
51
in SMT Connection between hardware (LDCM) and software (SMBI) is indicated by an X.
IEC10000245 V1 EN-US
Figure 51:
To rename a chosen Hardware Channel in SMT:
1.
Select the channel you want to rename.
2.
Open Object Properties.
3.
Rename the channel in the User Defined Name field and save.
IEC10000246 V1 EN-US
Figure 52: Renaming a channel in SMT
Communication set-up, 670/650 series
Application Guide
shows a configuration of LDCM Hardware Channel and SMBI in the Binary Inputs tab
Connection (indicated by X) established between LDCM and SMBI
© Copyright 2017 ABB. All rights reserved
Analog and binary signal transfer for line differential protection
IEC10000247-1-en.vsdx
IEC10000245-1-en.vsdx
IEC10000246-1-en.vsdx
Section 4
47