1MRK 505 382-UEN E
Table 1:
Setting
Operation
NoOfTerminals
IBase (Global base)
TransfAonInpCh
TraAWind1Volt
TraAWind2Volt
ClockNumTransA
TransfBonInpCh
TraBWind1Volt
TraBWind2Volt
ClockNumTransB
ZerSeqCurSubtr
Table 2:
Setting
ChargCurEnable
IdMin
EndSection1
EndSection2
SlopeSection2
SlopeSection3
Table continues on next page
Communication set-up, 670/650 series
Application Guide
General settings
IED 1
On
3
600 A
2
220 kV
70 kV
1
3
220 kV
70 kV
1
On
Setting group N
IED 1
Off
IBase
0.35 ·
1.25 ·
IBase
IBase
3.00 ·
40%
80%
© Copyright 2017 ABB. All rights reserved
Analog and binary signal transfer for line differential protection
IED 2
Description
On
Operation Mode (active)
3
Number of current sources/
circuit ends
600 A
Reference current of the
protection in the primary
system (note 1)
IBase is set in the Global
base values function
(GBASVAL).
1
Input currents on the input
channels are referred to the
high voltage side (note 2)
220 kV
Transformer A: Y-side
voltage
70 kV
Transformer A: d-side
voltage
1
LV d-side lags Y-side by 30
degrees
2
Input currents on the input
channels are referred to the
high voltage side (note 2)
220 kV
Transformer B: Y-side
voltage
70 kV
Transformer B: d-side
voltage
1
LV d-side lags Y-side by 30
degrees
On
Zero-sequence currents are
subtracted from
differential and bias
currents (note 3)
IED 2
Off
IBase
0.35 ·
1.25 ·
IBase
IBase
3.00 ·
40%
80%
Description
Charging current not
eliminated (default)
Sensitivity in Section 1
of the operate-
restrain characteristic
End of section 1 of the
operate-restrain
characteristic
End of section 2 of the
operate-restrain
characteristic
Slope of the operate-
restrain characteristic
in Section 2
Slope of the operate-
restrain characteristic
in Section 3
Section 4
33