1MRK 505 382-UEN E
IEC10000062 V1 EN-US
Figure 74: IED set as a slave
5.5.5.2
Service settings for transceiver 21–216
IEC07000256 V1 EN-US
Figure 75: Transceiver 21–216
Only one setting is required for transceiver 21–216. It has to be set to external clock. Rotary
switch on the front panel pointing to position 0 indicates that external clock is selected. If
back-to-back testing is to be performed, one transceiver 21-216 has to be set as master by
setting the rotary switch to position 2 (overrides settings of jumpers 8 and 9). Clock
synchronization configuration using the rotary switch can be done on the fly.
5.5.6
Earthing
The recommended earthing method is direct earthing. With earth loop problems, soft earth
method can be beneficial (see Figures
Communication set-up, 670/650 series
Application Guide
76
and 77).
© Copyright 2017 ABB. All rights reserved
Section 5
Communication set-up
GUID-4B6CB0C7-8F0E-4FE8-BD12-A3E03FE4FF72 v1
GUID-F03C51FF-418F-4761-BF4C-73833D10804D v1
75