Set Point - Carrier AquaForce B Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Variable speed air-cooled liquid chillers with greenspeed intelligence and carrier controller
Table of Contents

Advertisement

APPENDIX H — EVAPORATOR HEATER SENSOR SET POINT
TONNAGE
TIER
MODEL 12TH DIGIT
NO PUMP
140-180
ALL
200
S
200
M, H
225 - 325
All
350 - 500
All
Evaporator Heater Sensor Set Point
COOLER HEATER CSR SETTINGS
MODEL 12TH DIGIT
0,1,B
2,C
NO PUMP
5.2
5.2
5.2
5.2
10.4
5.2
10.4
10.4
10.4
10.4
SETPOINT [AMPS]
MODEL 12TH DIGIT
MODEL 12TH DIGIT
3
4,5,6,7,D,F,J,K,L,M
NO PUMP
5.2
n/a
5.2
10.4
10.4
332
MODEL 12TH DIGIT
8,9,G,N,P
PUMP OPTION
PUMP OPTION
10.4
10.4
10.4
10.4
15.6
10.4
15.6
15.6
n/a
n/a

Hide quick links: