APPENDIX I — CARRIER CONTROLLER WEB AND NETWORK INTERFACE PARAMETERS (cont)
5. Communication between the Carrier Controller controller
and the PC should be active. Using a standard Web Brows-
er, with minimum versions shown above and with Java in-
stalled, type in the IP address of the Carrier Controller con-
troller. The display on the PC should look very similar to
what is on the Carrier Controller controller display.
If issues still exist with accessing the Carrier Controller con-
troller using the web browser, try to ping the Carrier Controller
controller by using the following steps:
1. Open a command prompt using one of the following methods:
a. Window logo key + R to access the run command.
Then type CMD and press enter.
Or:
b. Click start button and then click run. Then type CMD
and press enter.
2. At the command prompt, type the ping command followed
by the unit IP address.
3. As shown in Fig. J, the device attached to IP address
161.145.71.145 communicated successfully. The IP ad-
dress for the Carrier Controller controller should return a
similar confirmation if the system is configured properly. If
it does not additional IT assistance may be necessary.
Fig. J — Ping Response Screen
335