Carrier AquaForce B Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 260

Variable speed air-cooled liquid chillers with greenspeed intelligence and carrier controller
Table of Contents

Advertisement

APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
SCRN_BRT — Screen Brightness Table
Carrier Controller PATH:
 Configuration Menu
Main Menu
LINE
DISPLAYED TEXT*
1
Adjust Display Brightness
USRPWCHG — User Password Change Table
Carrier Controller PATH:
 Configuration Menu
Main Menu
LINE
DISPLAYED TEXT*
1
Your login password
2
New user password
3
Confirm new user password
GEN_CONF — General Configuration Table
Carrier Controller PATH:
 Configuration Menu
Main Menu
LINE
DISPLAYED TEXT*
1
Cir Priority Sequence
2
Ramp Loading Enabled
3
Unit Off to On Delay
4
Demand Limit Type Select
5
Night Mode Start Hour
6
Night Mode End Hour
7
Night Capacity Limit
8
Ice Mode Enable
9
Short Cycle Management
LEGEND
RO — Read Only
RW — Read/Write
* Depends on the selected language (English by default).
 HMI Configuration
 Screen Brightness Table
CCN NAME
Very Low(0)
Low(1)
Medium(2)
High(3)
Very High(4)
 HMI Configuration
 User Password Change Table
CCN NAME
 General Configuration Table
CCN NAME
prio_cir
ramp_sel
off_on_d
lim_sel
nh_start
nh_end
nh_limit
ice_cnfg
shortcyc
260
DEFAULT
RANGE
VALUE
DEFAULT
RANGE
VALUE
DEFAULT
RANGE
VALUE
Auto(0)
A Priority(1)
0
B Priority(2)
No(0)/Yes(1)
Yes(1)
1 to 15
1
None(0)
Switch(1)
0
4-20mA(2)
0 to 23
0
0 to 23
0
0 to 100
100
No(0)/Yes(1)
No(0)
No(0)/Yes(1)
No(0)
READ/
UNIT
WRITE
RW
READ/
UNIT
WRITE
RW
RW
RW
READ/
UNIT
WRITE
RW
RW
min
RW
RW
RW
RW
RW
RW
%
RW
RW
RW