Carrier AquaForce B Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 58

Variable speed air-cooled liquid chillers with greenspeed intelligence and carrier controller
Table of Contents

Advertisement

THERMISTOR ID
EWT
Entering Water Temperature Thermistor
LWT
Leaving Water Temperature Thermistor
OAT
Outdoor Air Temperature Thermistor
SGTA
Circuit A Suction Gas Temperature Thermistor
SGTB
Circuit B Suction Gas Temperature Thermistor
DGTA
Circuit A Discharge Gas Temperature Thermistor
DGTB
Circuit B Discharge Gas Temperature Thermistor
LIQT_A
Circuit A Liquid Line Temperature Thermistor
LIQT_B
Circuit B Liquid Line Temperature Thermistor
ECTA
Circuit A Economizer Temperature Thermistor
ECTB
Circuit B Economizer Temperature Thermistor
DUAL
Dual Chiller Leaving Water Temperature Thermistor
Comp A Temp
Circuit A Compressor Motor Temperature Thermistor
Comp B Temp
Circuit B Compressor Motor Temperature Thermistor
SPT
Space Temperature Thermistor
Table 37 — Compressor Thermistor Temperature vs. Resistance
°F
–22
–13
–4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
131
140
149
158
167
176
185
194
203
212
221
230
239
248
257
266
275
284
293
302
Table 36 — Thermistor Identification
DESCRIPTION
°C
–30
–25
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
58
RESISTANCE AT 77°F (25°C)
5k 
5k 
5k 
5k 
5k 
5k 
5k 
5k 
5k 
5k 
5k 
5k 
5k 
5k 
10k 
Nominal Resistance, Ohms
88,500
65,210
48,535
36,477
27,665
21,162
16,325
12,696
9,950
7,854
6,245
5,000
4,029
3,266
2,664
2,185
1,802
1,493
1,244
1,042
CONNECTION POINT
SIOBA-J25-AI01
SIOBA-J25-AI02
SIOBA-J25-AI03
AUXA-J6-CH12
AUXB-J6-CH12
AUXA-J6-CH11
AUXB-J6-CH11
AUXA-J7-CH13
AUXB-J7-CH13
SIOBA-J25-AI05
SIOBB-J25-AI05
SIOBB-J25-AI03
SIOBA-J25-AI04
SIOBB-J25-AI04
EMM-J6-CH2
876
741
629
536
459
394
340
294
256
223
195
171
151
133
117
104
93

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents