APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
PUMPCONF — Pump Configuration Table
Carrier Controller PATH:
 Configuration Menu
Main Menu
LINE
DISPLAYED TEXT*
Evap Pumps Sequence
1
Pump Auto Rotation Delay
2
Pump Sticking Protection
3
Flow Check if Pump Off
4
RESETCFG — Reset Configuration Table
Carrier Controller PATH:
 Configuration Menu
Main Menu
LINE
DISPLAYED TEXT*
Cooling Reset Select
1
OAT No Reset Value
2
OAT Full Reset Value
3
Delta T No Reset Value
4
Delta T Full Reset Value
5
Current No Reset Value
6
Current Full Reset Value
7
Space T No Reset Value
8
Space T Full Reset Value
9
Cooling Reset Deg. Value
10
LEGEND
RW — Read/Write
* Depends on the selected language (English by default).
 Pump Configuration
CCN NAME
No Pump(0)
One Pump Only(1)
cpumpseq
Two Pumps Auto(2)
Pump#1 Manual(3)
Pump#2 Manual(4)
pump_del
24-3000
pump_per
No(0)/Yes(1)
pump_loc
No(0)/Yes(1)
 Reset Configuration Table
CCN NAME
None(0)
OAT(1)
cr_sel
Delta T(2)
4-20mA(3)
Space Temp(4)
oat_crno
14 to 125(-10 to 51.7)
oat_crfu
14 to 125(-10 to 51.7)
dt_cr_no
0 to 25(-17.8 to -3.9)
dt_cr_fu
0 to 25(-17.8 to -3.9)
v_cr_no
0 to 20
v_cr_fu
0 to 20
spacr_no
14 to 125(-10 to 51.7)
spacr_fu
14 to 125(-10 to 51.7)
cr_deg
-30 to 30(-34.4 to -1.1)
261
DEFAULT
RANGE
VALUE
Two Pumps
Auto(2)
48
No(0)
Yes(1)
DEFAULT
RANGE
VALUE
None(0)
14(-10)
14(-10)
0(-17.8)
0(-17.8)
0
0
14(-10)
14(-10)
0(-17.8)
READ/
UNIT
WRITE
RW
RW
Hours
RW
RW
READ/
UNIT
WRITE
RW
°F(°C)
RW
°F(°C)
RW
°F(°C)
RW
°F(°C)
RW
mA
RW
mA
RW
°F(°C)
RW
°F(°C)
RW
°F(°C)