Carrier AquaForce B Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 266

Variable speed air-cooled liquid chillers with greenspeed intelligence and carrier controller
Table of Contents

Advertisement

APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
MST_SLV — Master/Slave Configuration
Carrier Controller PATH:
 Configuration Menu
Main Menu
LINE
DISPLAYED TEXT*
Master/Slave Select
0=Disable
1
1=Master
2=Slave
Master Control Type
1=Local Control
2
2=Remote Control
3=CCN Control
3
Slave Address
Lead/Lag Select
0=Always Lead
4
1=Lag Once Failed Only
2= Lead/Lag Runtime Sel
5
Lead/Lag Balance Delta
6
Lead Lag Start Timer
7
Lead Pulldown Time
8
Start of Error Higher
9
Lag Minimum Running Time
Lag Unit Pump Control
10
0=Stop if Unit Stops
1=Run if Unit Stops
11
Chiller in Series
CP_ENABL — Compressor Enable
Carrier Controller PATH:
 Configuration Menu
Main Menu
LINE
DISPLAYED TEXT*
1
DISABLE COMPRESSORS
2
Compressor A Disable
3
Compressor B Disable
LEGEND
RW
— Read/Write
Spt
— Set Point
*Depends on the selected language (English by default).
 Master/Slave Configuration
CCN NAME
ms_sel
0 to 2
ms_ctrl
1 to 3
slv_addr
1 to 236
lead_sel
0 to 2
ll_bal_d
40 to 400
lstr_tim
2 to 30
lead_pul
0 to 60
3 to 18(-16.1 to -
start_dt
7.8)
lag_mini
0 to 150
lag_pump
0 to 1
ll_serie
No(0)/Yes(1)
 Compressor Enable
CCN NAME
en_cp_a
No(0)/Yes(1)
en_cp_b
No(0)/Yes(1)
266
DEFAULT
RANGE
VALUE
Disable(0)
Local Con-
trol(1)
2
0
168
10
0
4(-15.6)
0
0
No(0)
DEFAULT
RANGE
VALUE
No(0)
No(0)
READ/
UNIT
WRITE
RW
RW
RW
RW
Hours
RW
min
RW
min
RW
°F(°C)
RW
min
RW
RW
RW
READ/
UNIT
WRITE
RW
RW