Demand Limit - Carrier AquaForce B Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Variable speed air-cooled liquid chillers with greenspeed intelligence and carrier controller
Table of Contents

Advertisement

7
6
5
4
Cooling Reset
Deg. Value
3
(cr_deg)
2
1
0
6
0

Demand Limit

There are three types of demand limiting that can be config-
ured. The first type is through switch control, which will re-
duce the maximum capacity to up to 3 user-configurable per-
centages. The second type is by 4 to 20 mA signal input which
will reduce the maximum capacity linearly between 100% at a
4 mA input signal (no reduction) down to the user-configurable
level at a 20 mA input signal. The third type uses the CCN
Loadshed module and has the ability to limit the current oper-
ating capacity to maximum and further reduce the capacity if
required. Demand limit control can be based on a calculated
capacity level. If the Demand Limit is enabled and the current
capacity requirement meets or exceeds the current Demand
Limit level, the unit will unload and display Override #9: De-
mand Limit section on page 48.
If the demand limit percentage is set below minimum unit op-
eration, the unit will go into override mode. See Override #91:
Demand Limit section on page 48.
SWITCH CONTROLLED DEMAND LIMIT
The control system is capable of demand limit based on a field-
supplied switch for 1-step demand limit or 2 switches for 3-step
demand limit. One-step demand limit is standard. The 2 or 3-step
switch control of demand limiting requires the EMM. Demand
limit steps are controlled By two relay switch inputs field wired to
TB5-5 and TB5-14 for Switch 1 (LIM_SW1) and TB6-14 and
TB6-15 for Switch 2 (LIM_SW2).
For demand limit by switch control, closing the first demand
limit contact (LIM_SW1) will put the unit on the first demand
limit (LIMIT 1) by capacity. The unit will not exceed the per-
centage of capacity entered as Demand Limit Switch 1 set point.
Closing contacts on the second demand limit switch
(LIM_SW2) and opening the Demand Limit Switch 1 prevents
the unit from exceeding the demand limit (LIMIT 2) entered as
Demand Limit Switch 2 set point. If both demand limit switch
(LIM_SW1 and LIM_SW2) contacts are closed the unit will not
exceed the limit (LIMIT 3) set by the switch limit set point 3.
See the table below.
CONTACT
NONE
LIM_SW1
Open
LIM_SW2
Open
Space T Full Reset Value
(spahr_fu)
6
5
Space Temperature (deg F)
Fig. 42 — Example: Space Temperature Reset
ACTIVE DEMAND LIMIT
LIMIT 1
LIMIT 2
LIMIT 3
Close
Open
Close
Open
Close
Close
Space T No Reset Value
(spahr_no)
7
0
7
To use demand limit, select the type of demand limiting to use
by configuring the Demand Limit Select variable (Main Menu
Configuration Menu
Limit Type Select) to Switch. Configure the demand limit set
points based on the type selected.
If using 2 or 3-step demand limit control, an energy management
module must be installed. The energy management module must
be enabled in the controls. To enable the EMM navigate to Fac-
tory Parameters menu (Main Menu
Factory Parameters) and set Energy Management Module to
YES (1).One-step demand limit control does not require the en-
ergy management module. To configure demand limit for switch
control, three parameters for 1-step switch control must be con-
figured. For 2 or 3-step control, additional set point parameters
must be configured. The parameters are: the type of Demand
Limit Selection, the setting for Switch Limit Setpoint 1, the set-
ting for Switch Limit Setpoint 2 (if required) and the setting for
Switch Limit Setpoint 3 (if required).
To configure this option with the Carrier Controller display:
DISPLAY NAME
PATH
Main Menu
Configuration Menu
Demand Limit
Type Select
General Configura-
tion
Switch Limit
Main Menu
Setpoint 1
Setpoint Table
Main Menu
Switch Limit
Setpoint Table
Setpoint 2
Main Menu
Switch Limit
Setpoint Table
Setpoint 3
In the following example, 2-step demand limit based on capac-
ity is desired with the first switch closure limiting the capacity
to 60%. The second switch closure is to limit the capacity to
40%. Demand Limit Switch 1 is 60% and Demand Limit
Switch 2 is 40%. Since no third-step demand limit is required,
Switch Limit Setpoint 3 is set at 0%.
DISPLAY NAME
Demand Limit Type Select
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
44
5
80
a30-5884
General Configuration

Configuration Menu
VALUE
Default = 0 (None)
Range None = 0
Switch = 1
4 to 20mA = 2
Default = 100%
Range 0 to 100%
Default = 100%
Range 0 to 100%
(Not required for 1-Step Control)
Default = 100%
Range 0 to 100%
(Not required for 1 or 2-Step Control)
Demand
VALUE
1
60%
40%
0%

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents