6.6.2
Unlocking a security code
Select parameter to be edited
Press the
Press the
Enter the correct security code
Press the
If the correct security code has been entered, the display will flash and can now be
adjusted.
If the security code has been entered incorrectly, the above procedure should be
followed again.
6.6.3
Re-locking security
When a security code has been unlocked and the required parameter changes made, to
re-lock the same security code:
Set Pr 10 to LoC
Press the
6.6.4
Setting security back to 0 (zero) - no security
Set Pr 10 to L2
Go to Pr 25
Unlock security as described above.
Set Pr 25 to 0
Press the
6.7

Setting drive back to default values

Set Pr 10 to L2
Set Pr 29 to Eur and press the
or
Set Pr 29 to USA and press the
26
MODE key, the display will flash 'CodE'
M
UP key to start entering the set security code.
MODE key
M
STOP/RESET key
MODE key.
M
M
www.johnsoncontrols.com
MODE key. This loads 50Hz default parameters.
MODE key. This loads 60Hz default parameters.
M
VFD66 User Guide