4.3.4
Immunity Compliance
The level of the drives immunity from conducted and radiated emissions from external
sources is summarised below in Table 4-3.
Table 4-3 Immunity compliance
Standard
Type of immunity
IEC 61000-4-2
EN 61000-4-2
IEC 61000-4-3
Radio frequency
EN 61000-4-3
radiated field
IEC 61000-4-4
Fast transient
EN 61000-4-4
IEC 61000-4-5
EN 61000-4-5
IEC 61000-4-6
Conducted radio
EN 61000-4-6
IEC 61000-4-11
Voltage dips and
EN 61000-4-11
IEC 61000-6-1
Generic immunity standard for the residential,
EN 61000-6-
commercial and light – industrial environment
1:2007
IEC 61000-6-2
Generic immunity standard for the industrial
EN 61000-6-
environment
2:2005
IEC 61800-3
Product standard for adjustable speed power
EN 61800-3:2004
drive systems (immunity requirements)
VFD66 User Guide
Issue Number: 2
Test specification
Electrostatic
6kV contact discharge
discharge
8kV air discharge
10V/m prior to modulation
80 – 1000MHz
80% AM (1kHz)
modulation
5/50ns 2kV transient at
5kHz repetition
frequency via coupling
clamp
burst
5/50ns 2kV transient at
5kHz repetition frequency
by direct injection
Common mode 4kV
1.2/50µs waveshape
Differential mode 2kV
Surges
1.2/50µs waveshape
Lines to ground
10V prior to modulation
0.15 – 80MHz
frequency
80% AM (1kHz)
modulation
-30% 10ms
+60% 100ms
interruptions
-60% 1s
<-95% 5s
www.johnsoncontrols.com
Application
Module enclosure
Module enclosure
Control lines
(industrial harsh)
Power lines
AC supply lines:
Line to ground
AC supply lines:
Line to line
Signal ports to
ground
Control and power
lines
AC power ports
Meets immunity requirements for first and
second environments
Level
Level 3
(industrial)
Level 3
(industrial)
Level 4
Level 3
(industrial)
Level 4
Level 3
Level 2
Level 3
(industrial)
Complies
Complies
17