Electronic pressure transducer input mode
The VFD66 controls work with any electronic pressure transducer that generated a 0-5
Vdc or 0-10Vdc output signal.
The user can configure the drive using Set point (Pr 61) & Proportional Band (Pr 62) and
Max Speed (Pr 02). Note that Minimum Speed (Pr 67) and Action at Min Speed (Pr 64)
cannot be configured in this mode.
Figure 7-3 Electronic pressure transducer input mode Pr 05 = EPt
63
2 transducer
4
Analog
Input voltage
input 1
level 5/10V
5
Analog
input 2
Input voltage
level 5/10V
Key
X
Input terminals
XX.XX
Read-write parameter
XX.XX
Read-only parameter
The setpoint (0 to 95%) minus Proportional band (0 to 95%) value cannot be a negative
value.
RPM
100%
50%
40%
30%
20%
10%
0%
30
65
94
Analog
input 1
65
95
Analog
input 2
(200psi)
Min
Proportional Band (50psi)
www.johnsoncontrols.com
61
Set point
Proportional
62
band
Max speed
02
66
+
_
Comparator,
higher of the
two is selected
X-Axis
85
Motor
frequency
SS
(250psi)
SS
500psi
Pressure/
Max
temperature
Set point
VFD66 User Guide