GE AF-650 GP Operating Instructions Manual page 55

General purpose drive high power 460/575/690v 125hp and above
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

How to Program
4.1.2 Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up
procedure using Keypad (read table from left to right). The example applies to open loop applications.
Press
4
4
K-01 Language
K-02 Motor Speed Unit
P-02 Motor Power [HP] or P-07 Motor
Power [kW]
F-05 Motor Rated Voltage
F-04 Base Frequency
P-03 Motor Current
P-06 Base Speed
F-01 Frequency Setting 1
F-02 Operation Method
F-07 Accel Time 1
F-08 Decel Time 1
F-10 Electronic Overload
F-15 Motor Speed High Limit [Hz] or
F-17 Motor Speed High Limit [RPM]
F-16 Motor Speed Low Limit [Hz] or
F-18 Motor Speed Low Limit [RPM]
H-08 Reverse Lock
P-04 Auto Tune
54
AF-650 GP High Power Operating Instructions
Quick Start
Set language
Set motor speed in Hz or RPM
Set Motor nameplate power
Set Nameplate voltage
Set Nameplate frequency
Set Nameplate current
Set Nameplate speed in RPM
Set reference source
Select which reference site to activate
Set the accel time with reference to synchronous motor
speed, n
s
Set the decel time time with reference to synchronous
motor speed, n
s
Set motor thermal protection
Set motor speed high limit in Hz or RPM
Set motor speed low limit in Hz or RPM
Set allowed rotation direction
Set desired auto tune function. Enable complete auto
tune is recommended

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents