GE AF-650 GP Operating Instructions Manual page 86

General purpose drive high power 460/575/690v 125hp and above
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

General Specifications
Surroundings:
Enclosure, frame size 4X and 5X
Enclosure, frame size 5X
Vibration test
Max. relative humidity
Aggressive environment (IEC 60068-2-43
Ambient temperature (with SFAVM switching mode)
- with derating
- at full continuous drive output current
1) For more information on derating, see special conditions in the AF-650 GP Design Guide
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see special conditions in the AF-650 GP Design Guide
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the AF-650 GP Design Guide Please see www.geelectrical.com/drives for more information.
Protection and Features:
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the drive trips if the temperature reaches a predefined level.
An overload temperature cannot be reset until the temperature of the heatsink is below the values stated in the
tables on the following pages (Guideline - these temperatures may vary for different power sizes, Unit Sizes,
enclosure ratings etc.).
The drive is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the drive trips if the intermediate circuit voltage is too
low or too high.
The drive constantly checks for critical levels of internal temperature, load current, high voltage on the
intermediate circuit and low motor speeds. As a response to a critical level, the drive can adjust the switching
frequency and/ or change the switching pattern in order to ensure the performance of the drive.
AF-650 GP High Power Operating Instructions
IP00 Open Chassis, IP21/Nema 1, and IP54/Nema 12
5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
IP21/Nema 1, and IP54/Nema 12
Max. 55 °C
Max. 45 °C
-25 - +65/70 °C
EN 61800-3, EN 61000-6-3/4, EN 55011
EN 61800-3, EN 61000-6-1/2,
0.7 g
class H
5
2
1)
1)
0 °C
5
5
- 10 °C
1000 m
85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents