Operating Mode - ABB PowerValue 11 RT G2 IN User Manual

6-10 kva
Hide thumbs Also See for PowerValue 11 RT G2 IN:
Table of Contents

Advertisement

U S E R M A N U A L

4 .2 Operating mode

The following table describes the UPS status information:
Table 4: Symbols in operating mode
Status
LCD Screen
Online mode
ECO mode
Frequency
converter mode
Battery mode
Bypass mode
Standby mode
Overload
warning
Overload fault
Battery test
Description
When the input voltage is within acceptable range, UPS will provide
pure and stable AC power to output. The UPS will also charge the
battery in online mode.
Energy saving mode:
When the input voltage is within voltage regulation range, UPS will
bypass voltage to output for energy saving.
When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a
constant output frequency, 50 Hz or 60 Hz. The UPS will still charge
battery under this mode.
When the input voltage is beyond the acceptable range or power
failure and alarm are sounding every 4 second, UPS will backup power
from battery.
When input voltage is within acceptable range but UPS is overloaded,
UPS will enter bypass mode or bypass mode can be set from front
panel. Alarm sounds every 10 seconds.
UPS is powered off and no output supply power, but still can charge
batteries.
When the UPS is in overload, an alarm sounds twice every second.
will flash. Disconnect unnecessary loads one by one to decrease
the load. The load should be lower than 90 percent of its nominal
power capacity in order to stop alarming.
When the UPS is in overload fault, an alarm sounds continuously.
Overload icon will be on. At this time, UPS will stop operation and
there is no output power on receptacles.
Please check chapter 6.Troubleshooting to solve this problem.
UPS is performing a battery test.
21
will flash.