UNIT CONTROLLER
DHW Anti Legionella
•
Status
•
Operation Day
•
Starting Time
•
Setting Temperature
•
Duration
REF
Access
DesFun
Status
OpInt
Operation Day
StTim
Starting Time
SHWTS
Setting Temperature
KeepP
Duration
?
N O T E
•
(*1):If Status (DesFun)= "Enabled".
•
(*2): 70 or "A" if "A"<70.
•
(*) Refer to the table:
Model
A
- (1): 75 ºC when DHW tank's heater is enabled (DSW4-3: ON) or Combination mode (BOCM)= "Parallel" and DHW by boiler (BODHW)
"Enabled" in "Boiler combination" option of the "Complementary heating" menu.
- (2): If the conditions of (1) are no satisfied and the R-134a compressor is disabled (DSW4-1: ON) of the "Complementary heating" menu, the
setting must be 55 ºC.
151
PMML0335A rev.1 - 04/2016
Description
Anti Legionella
YUTAKI S & COMBI
(2.0-3.0)HP
REST
50ºC (1)
55ºC (1)
Default
Range
Value
Disabled /
Disabled
Enabled
Sunday
Daily / Mon ~ Sun
01:00
(00:00~ 23:50)
70 (*2)
50~A
10
10~60
YUTAKI S80
(4.0-6.0)HP
75ºC (2)
Steps
Units
Application
S
SC S80 M
-
-
○
○
○
-
day
○
○
○
00:10
time
○
○
○
-
ºC
○
○
○
-
min
○
○
○
YUTAKI M
3HP
50ºC (1)
55ºC (2)
Notes
○
-
○
(*1)
○
(*1)
○
(*1)(*)
○
(*1)
REST