ELECTRICAL AND CONTROL SETTINGS
7.4.2 Table board 2
Input and output terminals give the possibility to configure the installation according to the needs of the user. The default settings
and I/O terminals reach most of the options necessary for an optimal performance of the system. Additionally, the settings can be
modified through the unit controller, and input/output terminals can be used, if required, to have additional options.
Input terminals (Default input functions)
PC-ARFHE connection
In those cases where the unit controller is ordered as a required accessory (YUTAKI S80 or YUTAKI M), or those cases where
another PC-ARFHE must be connected as a second thermostat, the connections between PC-ARFHE and the indoor unit must be
done in terminals 3 and 4, as it is shown in the next picture:
4-20mA Setting Temperature
It is possible to connect an external controller to the terminals 11 and 12 to provide a manual water temperature setting. The input
current (4-20 mA) will be transformed into voltage by means of the ATW-MAK-01 accessory connected to these terminals. Settings
in Unit controller and in PCB have to be in Local mode (Enabled manual operation) to enable this function.
DHWT Thermistor (TDHWT)
For those cases in which a tank is installed as accessory, a thermistor must be installed to control the water temperature. The
connection for this thermistor must be done between terminals 5 and 6 of the TB2.
Water outlet thermistor for circuit 2 (TWO2)
When the installation is configured with a second circuit the thermistor for the water outlet temperature have to be connected
between terminals 6 and 7 of the terminal board 2.
104
PMML0335A rev.1 - 04/2016
3
4
A
B
OK
RCS H-LINK
(PC-ARFHE)
11
12
4-20mA
Setting temperature
6
5
T
DHWT
DHWT
6
7
T
wo2
Circuit 2