UNIT CONTROLLER
8.6.2.4 Space Heating
If Controller type (LCDM)= "Unit" or "Unit+Room".
•
Circuit 1
•
Circuit 2
Circuit 1 and Circuit 2
•
Water Calculation Mode
•
Eco offset
•
Working Limits
•
Mixing Valve
REF
Access
C1WC
Water Calculation Mode (Circuit 1)
C1ECO
ECO offset water set (Circuit 1)
C2WC
Water Calculation Mode (Circuit 2)
C2ECO
ECO offset water set (Circuit 2)
-
Working Limits (Circuit 1 and 2)
-
Mixing Valve (Circuit 2)
?
N O T E
(*1): If Water calculation mode for circuit 1 heating (C1WC) is not set as "Disabled".
(*2): If Water calculation mode for circuit 2 heating (C2WC) is not set as "Disabled".
(*3): If Water calculation mode for circuit 1 heating (C1WC) or Water calculation mode for circuit 2 heating (C2WC) are not set as "Disabled".
(*4): For YUTAKI S80 with DSW enabled for cooling, water calculation mode (Circuit 1) is set as "Fix".
144
PMML0335A rev.1 - 04/2016
Default
Description
Value
Circuit 1 and Circuit 2
Gradient
Disabled
Range
Steps
Disabled
Point
Gradient
Fix
3
1~10
Disabled
Point
Gradient
Fix
3
1~10
-
-
-
-
Units
Application
S
SC S80 M
1
-
○
○
○
1
ºC
○
○
○
1
-
○
○
○
1
ºC
○
○
○
-
-
○
○
○
-
-
○
○
○
Notes
○
(*4)
○
(*1)
○
-
○
(*2)
○
(*3)
○
(*2)