Jog Function - gefran ADV200 Manual

Field oriented vector ac drive for asyncronous motors
Table of Contents

Advertisement

9 – JOG FUNCTION
Menu
PAR
Description
9.1
910 Jog setpoint
The reference for Jog mode operation. This reference can also be set via an analog input. The Jog reference
is enabled when the signal used for the Jog + or Jog – command is enabled, the Run command is not present
and the drive output frequency is zero.
Menu
PAR
Description
9.2
912 Jog acceleration
9.3
914 Jog deceleration
Setting of the acceleration/deceleration ramp time (in seconds) used during Jog operation.
Menu
PAR
Description
9.4
916 Jog cmd + src
Selection of the origin (source) of the Jog + function enabling signal. When this command is enabled it gener-
ates a Jog Mode reference with a sign matching the value entered for the Jog setpoint value parameter. The
signal to be associated with this function can be selected from the "L_DIGSEL2" selection list.
Note !
The Run command has priority over the Jog + command.
Menu
PAR
Description
9.5
918 Jog cmd - src
Selection of the origin (source) of the Jog - function enabling signal. When this command is enabled the Jog
Mode reference sign is inverted with respect to the value entered in the Jog setpoint value parameter. The
signal to be associated with this function can be selected from the "L_DIGSEL2" selection list.
Note !
The Run command has priority over the Jog - command.
Menu
PAR
Description
9.6
920 Jog output mon
The speed reference used by the Jog command is displayed.
ADV200 • Functions description and parameters list
UM
Type
FB BIT
rpm
INT16
UM
Type
FB BIT
s
FLOAT
s
FLOAT
UM
Type
FB BIT
LINK
16
UM
Type
FB BIT
LINK
16
UM
Type
FB BIT
rpm
INT16 16/32
Def
Min
0
CALCI
Def
Min
5.0
0.01
5.0
0.01
Def
Min
6000
0
Def
Min
6000
0
Def
Min
0
0
Max
Acc
Mod
CALCI
RW
FVS
Max
Acc
Mod
1000.00
RW
FVS
1000.00
RW
FVS
Max
Acc
Mod
16384
RW
FVS
Max
Acc
Mod
16384
RW
FVS
Max
Acc
Mod
0
ER
FVS
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents