Emerson Rosemount 3051HT Quick Start Manual

Hygienic pressure transmitter with 4–20 ma hart revision 5 and 7 protocol
Hide thumbs Also See for Rosemount 3051HT:

Advertisement

Quick Links

Quick Start Guide
00825-0100-4091, Rev CB
February 2019
Rosemount
3051HT Hygienic Pressure
Transmitter
®
with 4–20 mA HART
Revision 5 and 7
Protocol

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 3051HT

  • Page 1 Quick Start Guide 00825-0100-4091, Rev CB February 2019 ™ Rosemount 3051HT Hygienic Pressure Transmitter ® with 4–20 mA HART Revision 5 and 7 Protocol...
  • Page 2 Quick Start Guide February 2019 NOTICE This guide provides basic guidelines for the Rosemount 3051HT Transmitter. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. WARNING Explosions could result in death or serious injury.
  • Page 3: System Readiness

    Verify the latest device driver (DD/DTM ) is loaded on your systems to ensure proper communications. • Download the latest device driver at Emerson.com or hartcomm.org. Rosemount 3051 device revisions and drivers Table 1-1 provides the information necessary to ensure you have the correct device driver and documentation for your device.
  • Page 4: Transmitter Installation

    Conduit entry orientation When installing a Rosemount 3051HT, it is recommended installing so a conduit entry faces downward or parallel to the ground to maximize drainability when cleaning.
  • Page 5: Set The Switches

    February 2019 Quick Start Guide Figure 2-1: In-line Protected Gage Vent Low Side Pressure Port Aluminum Polished 316 SST A. Low side pressure port (atmospheric reference) Clamping When installing clamp, follow recommended torque values provided by gasket manufacturer. Note To maintain performance, torquing a 1.5. Tri Clamp beyond 50 in-lb is not recommended on pressure ranges below 20 psi.
  • Page 6 • The cover must be fully engaged to comply with explosion-proof requirements. Example Figure 2-2: Transmitter Electronics Board Aluminum Without LCD display With LOI or LCD display Emerson.com/Rosemount...
  • Page 7: Connect The Wiring And Power Up

    February 2019 Quick Start Guide Polished 316 SST Without LCD display With LOI or LCD display A. Alarm B. Security Connect the wiring and power up Figure 2-3: Transmitter Wiring Diagrams (4–20 mA) - Aluminum A. 24 Vdc supply B. R ≥...
  • Page 8 CAUTION • Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 3051HT case is properly grounded. • Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.
  • Page 9 February 2019 Quick Start Guide 3. Ensure full contact with Terminal Block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw. Note The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.
  • Page 10 Connect the wiring and power up. When the transmitter is properly wired, refer to Figure 2-5 for internal and external transient grounding locations. Note The Rosemount 3051HT polished 316 SST housing only provides ground termination inside the terminal compartment. Emerson.com/Rosemount...
  • Page 11: Verify Configuration

    A Rosemount 3051 DD must be installed on the Field Communicator to verify configuration. Fast Key sequences for the latest DD are shown in Table 2-1. ™ For Fast Key sequences using legacy DD's, contact your local Emerson representative. Note Emerson recommends installing the latest DD to access the complete functionality. Visit Emerson.com/Field-Communicator...
  • Page 12 On an aluminum housing, buttons are located on the display and externally underneath the top metal tag. To activate the LOI, push any button. LOI button functionality is shown on the bottom corners of the display. See Table 2-2 Figure 2-6 for button operation and menu information. Emerson.com/Rosemount...
  • Page 13 February 2019 Quick Start Guide Table 2-2: LOI Button Operation Button Left SCROLL Right ENTER Figure 2-6: LOI Menu Assign PV HART Revision 2.4.3 Switch HART Revision mode If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 3051 will load a generic menu with limited Quick Start Guide...
  • Page 14: Trim The Transmitter

    The LRV is unaffected. The pressure value will be zero (on display and HART output). 4 mA point may not be at zero. • This requires the factory calibrated zero pressure is within a range of 3% of the URL [0 ± 3% × URL]. Example URV = 250 inH Emerson.com/Rosemount...
  • Page 15 February 2019 Quick Start Guide Applied Zero Pressure = ± 0.03× 250 inH O = ± 7.5 inH O (compared to factory settings) values outside this range will be rejected by the transmitter 2.5.1 Trimming with a Field Communicator Procedure 1.
  • Page 16 Perform trim with analog zero and span (option D4) Use the following procedure to perform a zero trim: Procedure 1. Set the transmitter pressure. 2. Press and hold the Zero button for two seconds to perform an analog zero trim. Emerson.com/Rosemount...
  • Page 17 February 2019 Quick Start Guide Perform trim with digital zero (option DZ) Use the following procedure to perform a zero trim: Procedure 1. Set the transmitter pressure. 2. Press and hold the Zero button for two seconds to perform a digital zero trim.
  • Page 18: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com. Ordinary Location Certification As standard, the transmitter has been examined and tested to determine that...
  • Page 19 February 2019 Quick Start Guide Standards: ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2. No.157-92, CSA Std. C22.2 No. 213 - M1987 Markings: Intrinsically Safe Class I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 03031-1024, Temperature Code T4;...
  • Page 20: Additional Certifications

    Zone 0. Additional Certifications ® All Rosemount 3051HT transmitters with the following connections are 3-A approved and labeled: T32: 1 1/2-in. Tri Clamp T42: 2-in. Tri Clamp...
  • Page 21 Ensure gasket selected for installation is approved to meet both application and EHEDG certification requirements. ASME-BPE All Rosemount 3051HT Transmitters with option F2 and the following connections are designed to ASME-BPE SF4 standards T32: 1 1/2-in. Tri Clamp T42: 2-in. Tri Clamp A self-certified certificate of compliance to ASME-BPE is also available (option Per Clause SD-2.4.4.2 (m), suitability of painted aluminum housings to be...
  • Page 22 Quick Start Guide February 2019 Figure 3-1: Rosemount 3051HT Declaration of Conformity EU Declaration of Conformity No: RMD 1106 Rev. G Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 declare under our sole responsibility that the product, Rosemount™ 3051HT Pressure Transmitters manufactured by, Rosemount, Inc.
  • Page 23 February 2019 Quick Start Guide Figure 3-2: Rosemount 3051HT Declaration of Conformity EU Declaration of Conformity No: RMD 1106 Rev. G EMC Directive (2014/30/EU) Models 3051HT Pressure Transmitters Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013 RoHS Directive (2011/65/EU) Models 3051HT Pressure Transmitters...
  • Page 24 Quick Start Guide February 2019 Figure 3-3: Rosemount 3051HT Declaration of Conformity EU Declaration of Conformity No: RMD 1106 Rev. G ATEX Notified Body SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland ATEX Notified Body for Quality Assurance SGS FIMCO OY [Notified Body Number: 0598] P.O.
  • Page 25 February 2019 Quick Start Guide Rosemount 3051HT China RoHS List of Rosemount 3051HT Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6)
  • Page 26 Quick Start Guide February 2019 Emerson.com/Rosemount...
  • Page 27 February 2019 Quick Start Guide Quick Start Guide...
  • Page 28 The Emerson logo is a Facebook.com/Rosemount trademark and service mark of Emerson Electric Youtube.com/user/ Co. Rosemount is mark of one of the Emerson RosemountMeasurement family of companies. All other marks are the Google.com/+RosemountMeasurement property of their respective owners.

Table of Contents