Setting Power Adjustment Parameters - Huawei SUN2000-63KTL-JPH0 User Manual

Hide thumbs Also See for SUN2000-63KTL-JPH0:
Table of Contents

Advertisement

SUN2000-63KTL-JPH0
User Manual
Parameter
Voltage rise
suppression reactive
adjustment point (%)
Voltage rise
suppression active
derating point (%)
Soft start time after
grid failure (s)
----End

7.6.1.4 Setting Power Adjustment Parameters

Procedure
Step 1 Choose Function Menu > Settings > Power Adjustment to set power adjustment
parameters.
Issue 04 (2019-06-30)
Description
The standards of certain countries and regions
require that the SUN2000 must generate a certain
amount of reactive power when the output
voltage exceeds a certain value.
This parameter is displayed when Voltage rise
suppression is set to Enable.
The standards of certain countries and regions
require that the SUN2000 must generate a certain
amount of reactive power when the output
voltage exceeds a certain value.
This parameter is displayed when Voltage
rise suppression is set to Enable.
The value of Voltage rise suppression active
derating point must be greater than that of
Voltage rise suppression reactive
adjustment point.
Specifies the time for the power to gradually
increase when the SUN2000 restarts after the
power grid recovers.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Value Range (Vn: rated
voltage)
[100, 115)
(100, 115]
[1, 1800]